SENSEPOINT RFD OPERATING MANUAL

8.2 System Status

Display indications, current output and relay states for various operational conditions
are shown in the following table. For further details of error messages and trouble
shooting see section 12.
Status
Display
Circuit or
'CELL' and 'F'
sensor error
flashing
Negative drift >
'CAL' and 'F'
5%
flashing
Negative drift<
'-0' flashing
5%
Normal
Gas concentration
Alarm 1
Gas concentration
'A1' flashing, LED
flashing.
Alarm 2
Gas concentration
'A2' flashing, LED
flashing.
Greater than full
Full scale reading
scale
flashing
Inhibit
Configuration icon
flashing
ROM check
'CRCP' and 'F'
error
flashing
RAM check
'CRCR' and 'F'
error
flashing
Data check
'CRCE' and 'F'
error
flashing
ADC Error
'Adc' and 'F'
flashing
System Status
Current
Output
0-1.5mA
2.5-3.2mA
3.2-4mA
4-20mA
4-20mA
4-20mA
>20mA
2 or 4mA
0-1.5mA
0-1.5mA
0-1.5mA
0-1.5mA
Table 5: System status
19
RFDMAN MAN0843 Issue 3
Relay
Relay 1 (per
Relay 2
menu P-02)
A2
A1
Active
Active
Active
Active
Per menu
Per menu P-04
P-05
Fault
Active
Active
Active
Active
Active
Active