Specification For The Repeat Panel - Honeywell 13270-01LB Data, Installation And Commissioning Manual

Fire control and repeat panels, conventional 1, 2, 4 and 8 zone panel range
Hide thumbs Also See for 13270-01LB:
Table of Contents

Advertisement

Fire Panels

Specification for the Repeat panel

Number of Zones
Colour
Assembled panel size (in mm)
Weight (with batteries) approximate
Operating temperature and humidity
Storage temperature and humidity
Approvals
Emission
Immunity
IP rating (BS5490)
Flush fixing kit
Mains operating voltage
Knock-In cable entry points
Terminal size
Battery supply (sealed lead acid)
Standby duration
User access: By means of code entry
via numeric key pad
(AL1 Authorised user - No code is
required)
Key pad button controls
Buzzer for local audible indications
Visual indications
Repeat panel (standard 8 zone)
Repeat panel connections
4188-424 issue 4_Part 1_10-09
Front cover - Grey RAL 7000
395 wide x 274 high x 87 deep
5.8kg (2.1Ah battery) / 6.2Kg (with 3.4Ah battery)
o
0 - 40
C low to +95% RH non condensing
o
-5
C to +50
BS EN50081-1:1992: Part 1 Residential, Commercial & Light industry
BS EN50130-4: 1996: Part 4 Alarm systems : Electromagnetic compatibility
Product family standard: Immunity requirements for components of fire ,
intruder and social alarm systems
13270-29 (Cut out required 378mm wide x 245mm high x 60mm deep)
2-off12V 2.1Ah - 3.4Ah (See applicable batteries as listed for Control panel
AL2 Site security
AL3 Site engineering
AL4 Engineers
Reset AL2 & AL3 codes
NOTE: Only a limited number of functions are accessible at the repeat panel .
Sound alarm, Silence alarm, System Reset & Cancel buzzer & numeric
keypad.
Fire & System Fault - continuous sound
(via piezoelectric buzzer operating at 2 or 2.5KHz 70dB(A) at 1m)
FIRE & ZONES-fire (Red LEDs 'lights')
ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, Test, Power,
Access/Function (Yellow LEDs 'lights')
Power on (Green LED 'lights')
Delay (LED 'lights')
A maximum of 1 repeat panel can be connected in series with the control
22
Specification for the Repeat panel
8 - Zone (standard size)
o
C low to +95% RH condensing
Not applicable
Class B limits
IP31 (indoor)
230V ac +10% -15% 50Hz
Top & back entries
2
2.5mm
maximum
72hr standby
3 digit code - 123
3 digit code - 321
4 digit code - 7426
4 digit code - 2623
Fault - intermittent sound
panel
via serial port