Operating Instructions For Access Level 4 Functions - Honeywell 13270-01LB Data, Installation And Commissioning Manual

Fire control and repeat panels, conventional 1, 2, 4 and 8 zone panel range
Hide thumbs Also See for 13270-01LB:
Table of Contents

Advertisement

Operating instructions for Access level 4 functions

To allow False Alarm Rejection On/Off (default is Off)
q Enter 3 digit AL3 code (default = 321), press shift, Enter 9000 007 followed by 000 to turn the false alarm
rejection algorithm Off.
q Enter 3 digit AL3 code (default = 321), press shift, Enter 9000 007 followed by 001 to turn the false alarm
rejection algorithm On.
To enter number of connected Repeat panels (default setting is 0) - TO BE SET AT MAIN PANEL
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 009 001
Operating instructions for Access level 4 functions
CAUTION: These AL4 functions are for trained engineers only and normally
access to these functions is NOT required.
How to set Non Latching Zone configuration (default setting is all zones are latching)
q A non latching zone fire condition will not action the auxiliary relay.
Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 032 and data as follows:
Decimal equivalent of eight bit number where a '1' signifies a latching zone and a '0' signifies a non latching
zone, also bit 0 corresponds to zone 1 and bit 7 corresponds to zone 8.
E.g. Requirement
All Zones non latching
Zone 1 latching, all others non latching
Zones 3,5,6 latching, all others non latching
All Zones latching
How to set Reset Silence Configuration (default silence alarms before reset)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 033 followed by 000 for a Reset Silences
and 001 for UK Linking.
How to set Sound/Resound alarms configuration (default is sound alarms at any time)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 034 followed by 000 for a Sound Alarms
at any time and 001 for Resound only.
How to set Zone short circuit configuration (default is short circuit seen as fault)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 035 data as follows:
Decimal equivalent of eight bit number where a '1' signifies a zone short circuit being seen as a fire and a '0'
signifies a zone short circuit being seen as a fault, also the bit 0 corresponds to zone 1 and bit 7 corresponds
to zone 8.
E.g. Requirement
For all Zones - short circuit signifies a fault
Zone 1 - short circuit signifies a fire
Zones 3,5&6 - short circuit signifies a fire
All Zones - short circuit signifies a fire
How to set the number of zones used (default is 8 zone)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 036 followed by data as follows:
001 for One zone panel, 002 for Two zone panel, 004 for Four zone panel and 008 for Eight zone panel.
How to change Charger Output level (default is 128)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 037 followed by a number between 000
and 255.
How to change the Reset Duration (default is 010)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 038 followed by a number between 000
and 100, in tenths of a second.
eight bit number
00000000
00000001
00110100
11111111
eight bit number
00000000
00000001
00110100
11111111
15
Fire Panels
data
000
001
052
255
data
000
001
052
255
4188-424 issue 4_Part 1_10-09