Specification For The Control Panel - Honeywell 13270-01LB Data, Installation And Commissioning Manual

Fire control and repeat panels, conventional 1, 2, 4 and 8 zone panel range
Hide thumbs Also See for 13270-01LB:
Table of Contents

Advertisement

Fire Panels

Specification for the Control panel

Note: Batteries are not supplied with some panels
Number of Zone (detection) circuits
Zone circuit voltage range
Zone circuit load (maximum)
Number of Sounder circuits
Sounder circuit (shared load)
Sounder circuit fuse
End-of-line unit
Flush fixing kit
Colour
Assembled panel size (in mm)
Weight (with batteries) approximate
Operating temperature and humidity
Storage temperature and humidity
Standards
Approvals
Emission
Immunity
IP rating (BS5490)
Knock-In cable entry points
Terminal size
Battery standby with 1mA load per
zone and 1A total sounder alarm load
Auxiliary contacts
(operates with fire)
Common Fault
Common Fire
Class change
24V Power supply
(Monitored)
User access: By means of code entry
via numeric key pad
(AL1 Authorised user - No code is
required)
Key pad button controls
Buzzer for local audible indications
Visual indications
Repeat panel connections
4188-424 issue 4_Part 1_10-09
1 - Zone panel
2 - Zone panel
Maximum Quiescent current: 3.0mA per zone OR
EN54 compliance limitation: 32 devices OR
Maximum of 20 diode bases per zone
(Short circuit current limited to < 20mA)
2
0.5A per output, 1A max shared load
@ 24V +2V -2V with mains present
(24V +2V -4V battery only)
Zone circuit: Capacitor (diode) unit Sounder circuit: 10K ohms resistor
OR Biploar Capacitor
13270-29 (Cut out required 378mm wide x 245mm high x 60mm deep)
Front cover - Grey RAL 7000 (standard)
395 wide x 274 high x 87 deep
5.8kg
o
0 - 40
o
-5
C to +50
EN54 Part 2:1997 + AMD 1 (and include optional clauses 7.8, 7.10 & 7.11) plus
EN54 Part 4:1997 + AMD 1 and AMD 2
BS EN50081-1:1992: Part 1 Residential, Commercial & Light industry
BS EN50130-4: 1996: Part 4 Alarm systems : Electromagnetic compatibility
Product family standard: Immunity requirements for components of fire , intruder
72hr standby plus 0.5hr with alarm load
Pair of normally closed (NC) and a pair of normally open (NO) contacts rated
1A @ 24V dc resistive load (Maximum 100m cable distance)
Open collector - normally On (35mA limit)
Open collector - normally Off (16mA limit)
Normally open push button, up to 100m cable distance away from the panel
250mA maximum at 24V dc +2V, -4V
AL2 Site security
AL3 Site engineering
AL4 Engineers
Reset AL2 & AL3 codes
Sound alarm, Silence alarm, System Reset & Cancel buzzer & numeric keypad.
Fire & System Fault - continuous sound
(via piezoelectric buzzer operating at 2 or 2.5KHz 70dB(A) at 1m)
FIRE & ZONES-fire (Red LEDs 'lights')
ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, Test, Power,
Access/Function (Yellow LEDs 'lights')
Power on (Green LED 'lights')
Delay ( Yellow LED 'lights')
via serial port, see also repeat panel specification
20
Specification for the Control panel
4 - Zone panel
19V to 25.5V
2
4
0.5A per output, 1A max shared load
@ 24V +2V -2V with mains present
(24V +2V -4V battery only)
0.75A resettable
5.8kg
5.8kg
C low to +95% RH non condensing
o
C low to +95% RH condensing
BSI approval acquired
Class B limits
and social alarm systems
IP31 (indoor)
13 - top & 13 - back
2
2.5mm
maximum
500mA maximum at 24V dc +1.5V, -4V
3 digit code - 123
3 digit code - 321
4 digit code - 7426
4 digit code - 2623
Fault - intermittent sound
8 - Zone panel
8
6.2kg