Universal Controller -
Coldroom
ZA-10003-YAD
Issue a : 5/11/96
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See 'Fault Finding'.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
There may be a controller with the same
name, already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Supervisor.
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
LA
Log probe alarm
Pn
probe 'n' faulty or not connected
(Where 'n' = probe number)
EE
EEPROM fault
rr
Internal program fault
E1
Plant fault 1
E2
Plant fault 2
ES
Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Parameter
Cut in Temperature
Differential Below
Control Weight
Display Weight
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod/Alm
OT Alarm
UT Alarm
Alarm Delay
Log OT Alarm
Log UT Alarm
Latch Alarm: 0=Off ; 1=On
Defrost Start
Number of Defrosts per Day
No Defrost Time
Gas Defrost Detect
Defrost Terminate Temperature
Defrost Minimum Time
Defrost Maximum Time
Drain Down Time
Defrost Min. Recovery Time
Defrost Max. Recovery Time
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas
Pump Down 1
Pump Down 2
Defrost Alarm Temp.
Defrost Mode: 0=Local ;
1=Remote
Defrost Hold: 0=Off ; 1=On
Pulse Defrost: 0=Off ; 1=On
Hour
Minute
Day
Month
Year
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
Door Alarm Delay
Drip Pan Heater: 0=Off ; 1=On
Fans Off when Door Open: 0=Off
1=On
Liquid Line Closed when Door
Open: 0=Off ; 1=On
Manual Defrost: 0=Off ; 1=On
Comments:
DIN
Range/Units
0
-49 to 30 / °C
1
0 to 30 / °C
2
0 to 100 / %
3
0 to 100 / %
8
0 to 3
5
-49 to 60 / °C
4
-49 to 60 / °C
6
00:00 to 99:00/Min:Sec
10
-49 to 60 / °C
9
-49 to 60 / °C
7
0 to 1
11
00:00 to 23:59/Hrs:Mins
12
0 to 6
13
0 to 25 / Hrs.
14
0 to 30 / °C
15
-49 to 30 / °C
16
00:00 to 99:00/Min:Sec
17
00:00 to 99:00/Min:Sec
18
00:00 to 20:00/Min:Sec
19
00:00 to 99:00/Min:Sec
20
00:00 to 99:00/Min:Sec
23
0 to 2
21
00:00 to 07:00/Min:Sec
22
00:00 to 07:00/Min:Sec
24
-49 to 60 / °C
25
0 to 1
26
0 to 1
27
0 to 1
28
0 to 23
29
0 to 59
30
0 to 31
31
0 to 12
32
0 to 99
33
0 to 2
34
00:00 to 99:00/Min:Sec
35
0 to 1
36
0 to 1
37
0 to 1
99
0 to 1
Default
Dsgn.
Act.
HT(LT)
0 (-20)
1.5 (2)
50
50
0
5 (-16)
-2 (-25)
20:00
5 (-15)
0 (-25)
0
01:00
6
7
18
10 (14)
05:00
24:00
(25:00)
01:30
20:00
30:00
0
00:00
00:00
20
0
0
0
0
20:00
0
0
0
0
YAD08c / 65EAEE