Universal Controller -
2 Section
ZA-10053-YAD
Issue a : 5/11/96
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See 'Fault Finding'.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
There may be a controller with the same
name, already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Supervisor.
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
LA
Log probe alarm
Pn
probe 'n' faulty or not connected
(Where 'n' = probe number)
EE
EEPROM fault
rr
Internal program fault
E1
Plant fault 1
E2
Plant fault 2
ES
Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Parameter
Cut in Temperature
Differential Below
Control Weight
Display Weight
Section 1: OT Alarm
Section 1: UT Alarm
Section 2: OT Alarm
Section 2: UT Alarm
Alarm Delay
Latch Alarm: 0=Off ; 1=On
Defrost Start
Number of Defrosts per Day
No Defrost Time
Section 1: Defrost Term. Temp.
Section 2: Defrost Term. Temp.
Defrost Minimum Time
Defrost Maximum Time
Defrost Min. Recovery Time
Defrost Max. Recovery Time
Drain Down Time
Defrost Alarm Temp.
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas
Defrost Mode: 0=Local ;
1=Remote
Defrost Hold: 0=Off ; 1=On
Pulse Defrost: 0=Off ; 1=On
Hour
Minute
Day
Month
Year
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
Lights/Blinds: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
Polarity: 0=N/O ; 1=N/C
Sunday (Blinds) Up / Down
Monday Up / Down
Tuesday Up / Down
Wednesday Up / Down
Thursday Up / Down
Friday Up / Down
Saturday Up / Down
Gas Alarm: 0=Off ; 1=On
Minor Leak
Major Leak
Manual Defrost: 0=Off ; 1=On
Comments:
DIN
Range/Units
0
-49 to 30 / °C
1
0 to 30 / °C
2
0 to 100 / %
3
0 to 100 / %
44
-49 to 60 / °C
45
-49 to 60 / °C
47
-49 to 60 / °C
48
-49 to 60 / °C
17
00:00 to 99:00/Min:Sec
18
0 to 1
4
00:00 to 23:59/Hrs:Mins
5
0 to 6
6
0 to 25 / Hrs.
46
-49 to 60 / °C
49
-49 to 60 / °C
7
00:00 to 99:00/Min:Sec
8
00:00 to 99:00/Min:Sec
9
00:00 to 99:00/Min:Sec
10
00:00 to 99:00/Min:Sec
11
00:00 to 20:00/Min:Sec
12
-49 to 60 / °C
13
0 to 2
14
0 to 1
15
0 to 1
16
0 to 1
19
0 to 23
20
0 to 59
21
0 to 31
22
0 to 12
23
0 to 99
24
0 to 2
25
0 to 3
26
0 to 1
27/28
00:00 to 23:59/Hrs:Mins
29/30
00:00 to 23:59/Hrs:Mins
31/32
00:00 to 23:59/Hrs:Mins
33/34
00:00 to 23:59/Hrs:Mins
35/36
00:00 to 23:59/Hrs:Mins
37/38
00:00 to 23:59/Hrs:Mins
39/40
00:00 to 23:59/Hrs:Mins
41
0 to 1
42
0 to 3500 / ppm.
43
0 to 3500 / ppm.
99
0 to 1
Default
Dsgn
Act.
HT(LT)
0 (-20)
1.5 (2)
50
50
5 (-16)
-2 (-25)
5 (-16)
-2 (-25)
20:00
0
01:00
6
7
10
10
05:00
24:00
(25:00)
20:00
30:00
01:30
20
0
0
0
0
0
0
0
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
0
50
200
0
YAD08t / 65EAEE