Honeywell 190797-YAD Installation Manual page 10

Tuscan universal controller

Advertisement

Universal Controller -
Dyadic
ZA-10005-YAD
Issue a : 5/11/96
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See 'Fault Finding'.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
There may be a controller with the same
name, already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Supervisor.
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
LA
Log probe alarm
Pn
probe 'n' faulty or not connected
(Where 'n' = probe number)
EE
EEPROM fault
rr
Internal program fault
E1
Plant fault 1
E2
Plant fault 2
ES
Energy-Saving Mode
Comments:
Store:............................................
Controller
Name:
Designer:.....................................
Date:............................................
Engineer:......................................
Date:.............................................
Parameter
Red Cycle Temperature
Red OT Alarm Temp.
Red UT Alarm Temp.
Defrost Type:0=Elect.;1=Off Cyc.
Yellow Cycle Temperature
Yellow OT Alarm Temp.
Yellow UT Alarm Temp.
Defrost Type:0=Elect.;1=Off Cyc.
White Cycle Temperature
White OT Alarm Temp.
White UT Alarm Temp.
Defrost Type:0=Elect.;1=Off Cyc.
Red Log OT Alarm
Red Log UT Alarm
Yellow Log OT Alarm
Yellow Log UT Alarm
White Log OT Alarm
White Log UT Alarm
Lead Cyc. Diff
Lag. Cut In
Lag Cut Out
Case Type: 0=Red ; 1=Yellow ;
2=White
Control Weight
Display Weight
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod./Alarm
Off Cycle Defrost Max.Temp.
Off Cycle Defrost Minimum Time
Off Cycle Defrost Maximum Time
Electric Defrost Max. Temp.
Electric Defrost Minimum Time
Electric Defrost Maximum Time
Defrost Start
Number of Defrosts per Day
No Defrost Time
Alarm Delay
Drain Down Time
Defrost Min. Recovery Time
Defrost Max. Recovery Time
Defrost Alarm Temp.
Defrost Mode: 0=Local ;
1=Remote
Defrost Hold: 0=Off ; 1=On
Pulse Defrost: 0=Off ; 1=On
Hour
Minute
Day
Month
Year
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
Lights/Blind: 0=Local ; 1=Remote
; 2=Man.Off ; 3=Man.On
Polarity: 0=N/O ; 1=N/C
Latch Alarm: 0=Off ; 1=On
Sunday (Blinds) Up / Down
Monday (Blinds) Up / Down
Tuesday (Blinds) Up / Down
Wednesday (Blinds) Up / Down
Thursday (Blinds) Up / Down
Friday (Blinds) Up / Down
Saturday (Blinds) Up / Down
Gas Alarm: 0=Off ; 1=On
Minor Leak
Major Leak
Manual Defrost: 0=Off ; 1=On
DIN
Range/Units
0
1 to 7 / °C
2
7 to 10 / °C
1
-3 to 4 / °C
3
0 to 1
4
-1 to 4 / °C
6
4 to 7 / °C
5
-6 to 1 / °C
7
0 to 1
8
4 to 12 / °C
10
11 to 14 / °C
9
1 to 6 / °C
11
0 to 1
20
8 to 10 / °C
19
-1 to 4 / °C
22
5 to 7 / °C
21
-2 to 1 / °C
24
12 to 14 / °C
23
3 to 7 / °C
12
0 to 30 / °C
13
0 to 3 / °C
14
0 to 3 / °C
16
0 to 2
15
0 to 100 / %
16
0 to 100 / %
18
0 to 3
30
-49 to 60 / °C
28
00:00 to 99:00/Min:Sec
29
00:00 to 99:00/Min:Sec
33
-49 to 60 / °C
31
00:00 to 99:00/Min:Sec
32
00:00 to 99:00/Min:Sec
26
00:00 to 23:59/Hrs:Mins
27
0 to 6
41
0 to 25/ Hrs.
Fixed / Min:Sec
34
00:00 to 03:00/Min:Sec
35
00:00 to 35:00/Min:Sec
36
15:00 to 35:00/Min:Sec
37
-49 to 60 / °C
38
0 to 1
40
0 to 1
39
0 to 1
42
0 to 23
43
0 to 59
44
0 to 31
45
0 to 12
46
0 to 99
47
0 to 2
48
0 to 3
49
0 to 1
25
0 to 1
50/51
00:00 to 23:59/Hrs:Mins
52/53
00:00 to 23:59/Hrs:Mins
54/55
00:00 to 23:59/Hrs:Mins
56/57
00:00 to 23:59/Hrs:Mins
58/59
00:00 to 23:59/Hrs:Mins
60/61
00:00 to 23:59/Hrs:Mins
62/63
00:00 to 23:59/Hrs:Mins
64
0 to 1
65
0 to 3500 / ppm.
66
0 to 3500 / ppm.
99
0 to 1
Default
Dsg
Act.
Setting
n.
4
8
2
0
1
5
-1
0
8
12
4
1
8
2
5
0
12
4
1.5
1
1
0
50
50
0
10
05:00
24:00
10
05:00
24:00
01:00
6
7
05:00
01:30
20:00
30:00
20
0
0
0
0
0
0
0
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
0
50
200
0
YAD08d / 65EAEE