Honeywell 190797-YAD Installation Manual page 4

Tuscan universal controller

Advertisement

Universal Controller -
Generic
ZA-10002-YAD
Issue a : 5/11/96
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See 'Fault Finding'.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
There may be a controller with the same
name, already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Supervisor.
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
LA
Log probe alarm
Pn
probe 'n' faulty or not connected
(Where 'n' = probe number)
EE
EEPROM fault
rr
Internal program fault
E1
Plant fault 1
E2
Plant fault 2
ES
Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Parameter
Cut in Temperature
Differential Below
Control Weight
Display Weight
Log Probe: 0=Off ; 1=Product ;
2=Alarm ; 3=Prod/Alm
OT Alarm
UT Alarm
Alarm Delay
Defrost Start
Number of Defrosts per Day
No Defrost Time
Log OT Alarm
Log UT Alarm
Latch Alarm: 0=Off ; 1=On
Gas Defrost Detect
Defrost Terminate Temperature
Defrost Minimum Time
Defrost Maximum Time
Drain Down Time
Defrost Min. Recovery Time
Defrost Max. Recovery Time
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas
Defrost Alarm Temp.
Defrost Mode: 0=Local ;
1=Remote
Defrost Hold: 0=Off ; 1=On
Pulse Defrost: 0=Off ; 1=On
Pump Down 1
Pump Down 2
Hour
Minute
Day
Month
Year
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
Lights/Blinds: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
Polarity: 0=N/O ; 1=N/C
Sunday (Blinds) Up / Down
Monday Up / Down
Tuesday Up / Down
Wednesday Up / Down
Thursday Up / Down
Friday Up / Down
Saturday Up / Down
Energy Saving: 0=Off ; 1=On
Entry Diff.
Exit Diff.
Exit Time
Cycle Temp.
Fan Diff.
Run on Time
Def. Term.
Gas Alarm: 0=Off ; 1=On
Minor Leak
Major Leak
Manual Defrost: 0=Off ; 1=On
Comments:
DIN
Range/Units
0
-49 to 30 / °C
1
0 to 30 / °C
2
0 to 100 / %
3
0 to 100 / %
8
0 to 3
5
-49 to 60 / °C
4
-49 to 60 / °C
6
00:00 to 99:00/Min:Sec
11
00:00 to 23:59/Hrs:Mins
12
0 to 6
27
0 to 25 / Hrs.
10
-49 to 60 / °C
9
-49 to 60 / °C
7
0 to 1
13
0 to 30 / °C
14
-49 to 30 / °C
15
00:00 to 99:00/Min:Sec
16
00:00 to 99:00/Min:Sec
17
00:00 to 20:00/Min:Sec
18
00:00 to 99:00/Min:Sec
19
00:00 to 99:00/Min:Sec
22
0 to 2
23
-49 to 60 / °C
24
0 to 1
26
0 to 1
25
0 to 1
20
00:00 to 07:00/Min:Sec
21
00:00 to 07:00/Min:Sec
28
0 to 23
29
0 to 59
30
0 to 31
31
0 to 12
32
0 to 99
33
0 to 2
34
0 to 3
35
0 to 1
36/37
00:00 to 23:59/Hrs:Mins
38/39
00:00 to 23:59/Hrs:Mins
40/41
00:00 to 23:59/Hrs:Mins
42/43
00:00 to 23:59/Hrs:Mins
44/45
00:00 to 23:59/Hrs:Mins
46/47
00:00 to 23:59/Hrs:Mins
48/49
00:00 to 23:59/Hrs:Mins
50
0 to 1
51
-49 to 60 / °C
52
-49 to 60 / °C
53
00:00 to 20:00/Min:Sec
54
-49 to 60 / °C
55
0 to 60 / °C
56
00:00 to 20:00/Min:Sec
57
-49 to 30 / °C
58
0 to 1
59
0 to 3500 / ppm.
60
0 to 3500 / ppm.
99
0 to 1
Default
Dsgn
Act.
HT(LT)
0 (-20)
1.5 (2)
50
50
0
5 (-16)
-2 (-25)
20:00
01:00
6
7
5 (-15)
0 (-25)
0
18
10 (14)
05:00
24:00
(25:00)
01:30
20:00
30:00
0
20
0
0
0
00:00
00:00
0
0
0
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
0
4
8
00:30
5
4
05:00
14
0
50
200
0
YAD08g / 65EAEE