Universal Controller -
Generic
ZA-10002-YAD
Issue a : 5/11/96
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See 'Fault Finding'.
Fault Finding:
Set-up Unit does not reach the first
screen.
•
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
•
There may be a controller with the same
name, already logged on the network.
•
There may be a maximum 32 controllers
already on the network segment.
•
Check on the InTouch panel, P.C. or
Supervisor.
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
LA
Log probe alarm
Pn
probe 'n' faulty or not connected
(Where 'n' = probe number)
EE
EEPROM fault
rr
Internal program fault
E1
Plant fault 1
E2
Plant fault 2
ES
Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Parameter
Cut in Temperature
Differential Below
Control Weight
Display Weight
Log Probe: 0=Off ; 1=Product ;
2=Alarm ; 3=Prod/Alm
OT Alarm
UT Alarm
Alarm Delay
Defrost Start
Number of Defrosts per Day
No Defrost Time
Log OT Alarm
Log UT Alarm
Latch Alarm: 0=Off ; 1=On
Gas Defrost Detect
Defrost Terminate Temperature
Defrost Minimum Time
Defrost Maximum Time
Drain Down Time
Defrost Min. Recovery Time
Defrost Max. Recovery Time
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas
Defrost Alarm Temp.
Defrost Mode: 0=Local ;
1=Remote
Defrost Hold: 0=Off ; 1=On
Pulse Defrost: 0=Off ; 1=On
Pump Down 1
Pump Down 2
Hour
Minute
Day
Month
Year
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
Lights/Blinds: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
Polarity: 0=N/O ; 1=N/C
Sunday (Blinds) Up / Down
Monday Up / Down
Tuesday Up / Down
Wednesday Up / Down
Thursday Up / Down
Friday Up / Down
Saturday Up / Down
Energy Saving: 0=Off ; 1=On
Entry Diff.
Exit Diff.
Exit Time
Cycle Temp.
Fan Diff.
Run on Time
Def. Term.
Gas Alarm: 0=Off ; 1=On
Minor Leak
Major Leak
Manual Defrost: 0=Off ; 1=On
Comments:
DIN
Range/Units
0
-49 to 30 / °C
1
0 to 30 / °C
2
0 to 100 / %
3
0 to 100 / %
8
0 to 3
5
-49 to 60 / °C
4
-49 to 60 / °C
6
00:00 to 99:00/Min:Sec
11
00:00 to 23:59/Hrs:Mins
12
0 to 6
27
0 to 25 / Hrs.
10
-49 to 60 / °C
9
-49 to 60 / °C
7
0 to 1
13
0 to 30 / °C
14
-49 to 30 / °C
15
00:00 to 99:00/Min:Sec
16
00:00 to 99:00/Min:Sec
17
00:00 to 20:00/Min:Sec
18
00:00 to 99:00/Min:Sec
19
00:00 to 99:00/Min:Sec
22
0 to 2
23
-49 to 60 / °C
24
0 to 1
26
0 to 1
25
0 to 1
20
00:00 to 07:00/Min:Sec
21
00:00 to 07:00/Min:Sec
28
0 to 23
29
0 to 59
30
0 to 31
31
0 to 12
32
0 to 99
33
0 to 2
34
0 to 3
35
0 to 1
36/37
00:00 to 23:59/Hrs:Mins
38/39
00:00 to 23:59/Hrs:Mins
40/41
00:00 to 23:59/Hrs:Mins
42/43
00:00 to 23:59/Hrs:Mins
44/45
00:00 to 23:59/Hrs:Mins
46/47
00:00 to 23:59/Hrs:Mins
48/49
00:00 to 23:59/Hrs:Mins
50
0 to 1
51
-49 to 60 / °C
52
-49 to 60 / °C
53
00:00 to 20:00/Min:Sec
54
-49 to 60 / °C
55
0 to 60 / °C
56
00:00 to 20:00/Min:Sec
57
-49 to 30 / °C
58
0 to 1
59
0 to 3500 / ppm.
60
0 to 3500 / ppm.
99
0 to 1
Default
Dsgn
Act.
HT(LT)
0 (-20)
1.5 (2)
50
50
0
5 (-16)
-2 (-25)
20:00
01:00
6
7
5 (-15)
0 (-25)
0
18
10 (14)
05:00
24:00
(25:00)
01:30
20:00
30:00
0
20
0
0
0
00:00
00:00
0
0
0
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
0
4
8
00:30
5
4
05:00
14
0
50
200
0
YAD08g / 65EAEE