JADE™ ECONOMIZER MODULE
PC MOD Tool (optional)
The PC MOD tool is connected to a personal computer and
communicates with the Jade economizer controller via the
Sylk bus. The W7220 PCMOD tool software is free and can
be downloaded from the url in the Accessories section.
Some features on the Jade controller can only be enabled
or disabled using the W7220 PC MOD tool. See the PC
MOD tool options section in Table 5.

SPECIFICATIONS

W7220A Economizer Module
The module is designed for use with any Honeywell 2 to 10
Vdc or Honeywell Sylkbus communicating actuator. The
module includes terminals for a CO
sensor, and an Outdoor Dry Bulb sensor. Enthalpy and
other options are available with Sylk Bus sensors.
User Interface: Provides status for normal operation,
setup parameters, checkout tests, and alarms and error
conditions with a 2-line 16 character LCD display and a
four button keypad.
Electrical
Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer: 100 VA maximum system input
Nominal Power Consumption (at 24 Vac, 60 Hz): 11.5
VA without sensors or actuators
Relay Digital Output Rating at 30 Vac (maximum power
from Class 2 input only): 1.5A run;
3.5A inrush @ 0.45PF (200,000 cycles) or
7.5A inrush @ 0.45PF (100,000 cycles)
External Sensors Power Output: 21 Vdc +/- 5% @ 48mA
IMPORTANT
All inputs and outputs must be Class 2 wiring.
Inputs
SENSORS:
NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor
for dry bulb change over or an OA Sylkbus sensor
for outdoor enthalpy change over is required in
addition to the MA sensor. An additional Return
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further
information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone direc-
tory).
2. Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China,
Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
63-2700—11
sensor, Mixed Air
2
2
Air (RA) Sylkbus sensor can be added to the
system for differential enthalpy or dry bulb
changeover. For differential dry bulb changeover
a 20k ohm sensor is required in the OA and a
Sylkbus sensor in the RA. Dip switch on RA
Sylkbus sensor must be set in the RA position.
Dry Bulb Temperature (optional) and Mixed Air
(required), C7250A:
2-wire (18 to 22 AWG);
Temperature range -40 to 150 °F (-40 to 65 °C).
Temperature accuracy -0°F/+2°F
Temperature and Humidity, C7400S1000 (optional):
Sylk Bus; 2-wire (18 to 22 AWG)
Temperature: range -40 to 150 °F (-40 to 65 °C)
Temperature accuracy -0°F/+2°F
Humidity: range 0 to 100% RH with 5% accuracy.
NOTE: Up to three (3) SYLK Bus sensors may be
connected to the JADE™ Economizer module. For
outdoor air (OA), return air (RA) and discharge
(supply) air (DA).
DCV (CO
) Sensor (C7232 or C7632):
2
2-10 Vdc control signal; minimum impedance >50k
ohm.
4 Binary inputs:
1-wire 24 Vac + common GND (see page 6 for wiring
details). 24 Vac power supply: 20 to 30 Vac 50/60Hz;
100 VA Class 2 transformer.
Outputs
Actuator signal: 2-10 Vdc; minimum actuator impedance
is 2k ohm; Sylkbus two-wire output for Honeywell
Sylkbus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O:
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
Environmental
Operating Temperature: -40 to 150 °F (-40 to 65 °C).
Exception of display operation down to -4 °F with full
recovery at -4 °F from exposure to -40 °F
Storage Temperature: -40 to 150 °F (-40 to 65 °C)
Shipping Temperature: -40 to 150 °F (-40 to 65 °C)
Relative Humidity: 5% to 95% RH non-condensing