Honeywell JADE W7220 Installation Instructions And Operators Manual page 19

Economizer module
Hide thumbs Also See for JADE W7220:
Table of Contents

Advertisement

Menu
Parameter
STATUS
ECON AVAIL
ECONOMIZING
OCCUPIED
HEAT PUMP
COOL Y1-IN
COOL Y1-OUT
COOL Y2-IN
COOL Y2-OUT
MA TEMP
DA TEMP
OA TEMP
OA HUM
RA TEMP
RA HUM
IN CO2
DCV STATUS
DAMPER OUT
ACT POS
ACT COUNT
ACTUATOR
EXH1 OUT
Table 5. Menu Structure
Parameter
Parameter
Range and
Default
b
Value
Increment
NO
YES/NO
NO
YES/NO
NO
YES/NO
COOL
c
n/a
HEAT
OFF
ON/OFF
OFF
ON/OFF
OFF
ON/OFF
OFF
ON/OFF
_ _._ ºF
-40 to 150 ºF Displays value of measured mixed air from MAT sensor. Displays --.- if
_ _._ ºF
-40 to 150 ºF Displays when Discharge Air Sylk Bus sensor is connected and displays
_ _._ ºF
-40 to 140 ºF Displays measured value of outdoor air temperature.
_ _ %
0 to 100%
_ _._ ºF
0 to 140 ºF
_ _ %
0 to 100%
_ _ _ ppm
0 to 2000
ppm
n/a
ON/OFF
2.0V
2.0 to 10.0 V Displays output voltage or position to the damper actuator.
n/a
0 to 100%
n/a
1 to 65,535
n/a
OK/Alarm
(on Alarm
menu)
OFF
ON/OFF
19
JADE™ ECONOMIZER MODULE
a
.
Notes
YES = economizing available; the system can use Outdoor Air for free
cooling when required.
YES = Outdoor Air being used for 1
YES = OCC signal received from space thermostat or unitary controller.
YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC.
Displays COOL or HEAT when system is set to heat pump (non-
conventional)
Y1-I signal from space thermostat or unitary controller for cooling
stage 1.
ON = 24 Vac on term Y1-I
OFF = 0 Vac on term Y1-I
Cool Stage 1 Relay Output to mechanical cooling (Y1-OUT terminal).
Y2-I signal from space thermostat or unitary controller for second
stage cooling.
ON = 24 Vac on term Y2-I
OFF = 0 Vac on term Y2-I
Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT terminal).
not connected, short, or out- of-range.
measured discharge air temperature.
Displays --.-°F if sensor sends invalid value, if not connected, short or
out-of-range.
Displays --°F if sensor sends invalid value, if not connected, short or
out-of-range.
Displays measured value of outdoor humidity from OA Sylkbus sensor.
Displays --% if not connected, short, or out- of-range.
Displays measured value of return air temperature from RA Sylkbus
sensor. Displays --°F if sensor sends invalid value, if not connected,
short or out-of-range.
Displays measured value of return air humidity from RA Sylkbus
sensor. Displays --% if sensor sends invalid value, if not connected,
short or out-of-range.
Displays value of measured CO2 from CO2 sensor. Invalid if not
connected, short or out-of-range. May be adjusted in Advanced menu
by Zero offset and Span. See note on page 6 concerning C7632
sensor.
Displays ON if above setpoint and OFF if below setpoint, and ONLY if a
CO2 sensor is connected.
Displays actual position of actuator.
Displays number of times actuator has cycled. 1 Cycle equals the sum
of 180° of movement in any direction.
Displays Error if voltage or torque is below actuator range
Output of EXH1 terminal. Displays ON when damper position
reaches programmed percentage setpoint.
ON = 24 Vac Output; OFF = No Output.
st
stage cooling.
e
63-2700—11