Honeywell JADE W7220 Installation Instructions And Operators Manual page 26

Economizer module
Hide thumbs Also See for JADE W7220:
Table of Contents

Advertisement

JADE™ ECONOMIZER MODULE
Table 6. Damper minimum position settings and readings on checkout menu.
Fan Speed
1
1
2
2
1
1
2
2
2
2
SEQUENCE OF OPERATION
OA Good to
DCV
economize?
None
No
None
Yes
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the
delay if the call for Y1-I and Y2-I have not been satisfied.
OA Good to
DCV
economize?
Below CO2
No
set
Yes
Above CO2
No
set
63-2700—11
Demand Control Ventilation
(CO2 Sensor)
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
Table 7. Dry Bulb Operation No DCV (CO2 sensor) - 1 Speed Fan.
Y1-I
Y2-I
FAN SPD
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Table 8. Dry Bulb Operation With DCV (CO2 sensor) - 1 Speed Fan.
Y1-I
Y2-I
FAN SPD
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
On
On
High
Off
Off
High
On
Off
High
Setpoints
MIN POS
N/A
MIN POS H
MIN POS L
VENT MIN
VENT MAX
VENT MIN H
VENT MAX H
VENT MINL
VENT MAX L
Y1-O
Y2-O
0-v/Off
0-v/Off
24-v/On
0-v/Off
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
24-v/On
a
0-v/Off
Y1-O
Y2-O
0-v/Off
0-v/Off
24-v/On
0-v/Off
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
24-v/On
a
0-v/Off
0-v/Off
0-v/Off
24-v/On
0-v/Off
26
Checkout
VMAX-HS
N/A
VMAX-HS
VMAX-LS
VMIN-HS
VMAX-HS
VMIN-HS
VMAX-LS
N/A
N/A
Occupied
Unoccupied
MIN POS
Closed
MIN POS
Closed
MIN POS
Closed
MIN POS
Closed
MIN POS to Full-
Closed to Full-Open
Open
MIN POS to Full-
Closed to Full-Open
Open
Occupied
Unoccupied
VENTMIN
Closed
VENTMIN
Closed
VENTMIN
Closed
VENTMIN
Closed
VENTMIN to Full-
Closed to Full-Open
Open
VENTMIN to Full-
Closed to Full-Open
Open
VENTMIN to
Closed
VENTMAX
VENTMIN to
Closed
VENTMAX