Honeywell JADE W7220 Installation Instructions And Operators Manual page 29

Economizer module
Hide thumbs Also See for JADE W7220:
Table of Contents

Advertisement

OA Good to
DCV
economize?
Yes
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the
delay if the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to
try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before
the first stage mechanical cooling is enabled.
Table 14. Enthalpy Operation With DCV (CO2 sensor) - 2 Speed Fan.
OA Good to
DCV
economize?
Below set No
Yes
Above set No
Yes
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the
delay if the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to
try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before
the first stage mechanical cooling is enabled.
Y1-I
Y2-I
FAN SPD
On
On
High
Off
Off
Low
On
Off
Low
On
On
High
Y1-I
Y2-I
FAN SPD
Off
Off
Low
On
Off
Low
On
On
High
Off
Off
Low
On
Off
Low
On
On
High
Off
Off
Low
On
Off
Low
On
On
High
Off
Off
Low
On
Off
Low
On
On
High
Y1-O
Y2-O
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
b
a
DELAY
0-v/Off
24-v/On
Y1-O
Y2-O
0-v/Off
0-v/Off
24-v/On
0-v/Off
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
24-v/On
a
0-v/Off
0-v/Off
0-v/Off
24-v/On
0-v/Off
24-v/On
24-v/On
0-v/Off
0-v/Off
0-v/Off
0-v/Off
b
a
DELAY
0-v/Off
24-v/On
29
JADE™ ECONOMIZER MODULE
Occupied
Unoccupied
MIN POS H
Closed
MIN POS L
Closed
MIN POS L to Full-
Closed to Full-Open
Open
MIN POS H to Full-
Closed to Full-Open
Open
Occupied
Unoccupied
VENTMIN L
Closed
VENTMIN L
Closed
VENTMIN H
Closed
VENTMIN L
Closed
VENTMIN L to
Closed to Full-Open
Full-Open
VENTMIN H to
Closed to Full-Open
Full-Open
VENTMIN L to
Closed
VENTMAX
VENTMIN L to
Closed
VENTMAX
VENTMIN H to
Closed
VENTMAX
VENTMIN L to
Closed
VENTMAX
VENTMIN L to
Closed to Full-Open
Full-Open
VENTMIN H to
Closed to Full-Open
Full-Open
63-2700—11