Profinet Controller Specifications - GE IC695PNC001 User Manual

Programmable control products pacsystems rx3i profinet controller
Hide thumbs Also See for IC695PNC001:
Table of Contents

Advertisement

PROFINET Controller Specifications

PROFINET Support
CPU Compatibility
Power Requirements
Operating Temperature Range 0 to 60°C maximum surrounding air temperature without a fan.
Number of Port Connectors
Micro USB Connector
LAN
Maximum I/O Memory
CPU Status Bits
PROFINET IO-Device Data
Update Rates on the
PROFINET Network
Number of IP addresses
Number of MAC Addresses
System Maximum Limits
PROFINET Controllers per RX3i
CPU
IO-Devices per IO-Controller
IO-Devices per Network
IO-Devices per RX3i CPU
IO-Controllers per network
Number of PROFINET Slots per
device
Number of PROFINET Subslots
per slot
Number of PROFINET
Submodules per RX3i CPU
Programmer Limits
Number of IO-Controllers
Number of IO-Devices
Total number of devices
Hot-swappable
For product standards, general operating specifications, and installation requirements, refer to the PACSystems RX3i
System Manual, GFK-2314.
GFK-2571A
PROFINET Version 2.2 General Class A IO-Controller
Requires CPU315 or CPU320, with firmware version 7.0 or higher.
3.3V: 0.5 A with no SFP devices installed
1.2 A maximum (2 SFP devices installed, 0.35 A per SFP device)
5V:
1.5 A maximum
A lower maximum temperature may be required depending on PNC
location and SFP population. Refer to ―Maximum Surrounding Air
Temperature Derating‖ on page 1-4.
Two RJ-45 and Two SFP Cages
(SFP devices not included, available separately.)
One, for communication with a computer using Command Line Interface.
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100/1000 Mbps
128 Kbytes of combined input/output memory per PROFINET Controller
32
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms
and 512ms
One
Five. One per external port and one internal.
4. Must be located in main rack. Cannot be located in a remote node.
64 per PROFINET Controller at maximum update interval. For limits at
shorter update intervals, refer to ―PNC Loading Limits‖ in chapter 3.
128 per network, spread across up to 8 IO-Controllers
128 per RX3i CPU, spread across up to 4 PROFINET Controllers
8
256
256
2048
128 (32 RX3i CPU targets × 4 IO-Controllers per RX3i CPU)
2048 (128 per network × 16 PROFINET networks)
2176 (does not include backplanes, power supplies, or I/O modules)
Yes
Chapter 1 Introduction
1
1-3

Hide quick links:

Advertisement

Table of Contents
loading