Configuration Tools - GE IC695PNC001 User Manual

Programmable control products pacsystems rx3i profinet controller
Hide thumbs Also See for IC695PNC001:
Table of Contents

Advertisement

3

Configuration Tools

Proficy Machine Edition is the primary tool used to configure an RX3i PROFINET network. In
addition, certain parameters can be set from a computer through the PNC's Command Line
Interface.
The Command Line Interface can be used to set the PNC's non-volatile parameters, which are listed
below. These parameters are initially set up in the Machine Edition configuration. If any of these
parameters is subsequently changed from the Command Line Interface, the module uses the new
setting. Regardless of their source, the module retains these non-volatile parameter settings over
power cycles.
Non-Volatile Configuration Parameters
Parameter
IP Address
Subnet Mask
Default Gateway
Device Name
Redundant Media
Role
Redundant Media
Ring Port 1 ID
Redundant Media
Ring Port 2 ID
Redundant Media
test interval
Redundant Media
monitor count
PACSystems* RX3i PROFINET Controller Manual – December 2011
3-4
Description
IP Address of the PNC.
Subnet mask of the PNC.
Default Gateway for the PNC.
PNC's PROFINET Device Name. Defaults to
empty string - indicating the PNC is not named.
Specifies whether media redundancy is disabled
or if it is enabled as a Client or if it is enabled as a
Manager.
Indicates one of the two network ports involved in
Media Redundancy. Valid values are 1 to 4.
Indicates one of the two network ports involved in
Media Redundancy. Valid values are 1 to 4.
Interval for sending test frames on ring ports in
millisecond units. Valid values are 1 to 1000.
Indicates the number of consecutive failed test
frames before declaring a ring failure. Valid
values are 2 to 10.
Default Value
0.0.0.0
0.0.0.0
0.0.0.0
""
Disabled
1
2
20 ms
3
GFK-2571A