GE IC695PNC001 User Manual page 105

Programmable control products pacsystems rx3i profinet controller
Hide thumbs Also See for IC695PNC001:
Table of Contents

Advertisement

Group/
Category/
Description
Type/
Description
28-49-0-0
Diagnosis Disappears
PROFINET Alarm
received.
28-50-0-0
PROFINET Status
Alarm received.
28-51-0-0
PROFINET Update
Alarm received.
28-52-0-0
Port Data Change
PROFINET Alarm
received (Alarm
contains
manufacturer specific
data).
28-53-x-0
Port Data Error
Appears PROFINET
Alarm received.
28-54-x-0
Port Data Error
Disappears
PROFINET Alarm
received.
28-55-x-y
Port Data Error
Appears PROFINET
Alarm received
(Alarm contains
Extended Channel
Data).
28-56-x-y
Port Data Error
Disappears
PROFINET Alarm
received (Alarm
contains Extended
Channel Data).
28-57-x-y
Port Data Error
Appears PROFINET
Alarm received
(Alarm contains
Qualified Channel
Data).
GFK-2571A
Cause
A PROFINET Alarm has been
received indicating that a
diagnostic condition has been
resolved on the PROFINET
device.
A PROFINET Alarm has been
received indicating a status
change on the PROFINET
Device.
A PROFINET Alarm has been
received indicating a change to
an operating parameter has
been changed outside of the
PNC's control.
A PROFINET Alarm has been
received indicating a Port
change on the PROFINET
device.
A PROFINET Alarm has been
received indicating that a Port
Error has occurred on the
PROFINET device.
A PROFINET Alarm has been
received indicating that a Port
Error condition has been
resolved on the PROFINET
device.
A PROFINET Alarm has been
received indicating that a Port
Error has occurred on the
PROFINET device.
A PROFINET Alarm has been
received indicating that a Port
Error condition has been
resolved on the PROFINET
device.
A PROFINET Alarm has been
received indicating that a Port
Error has occurred on the
PROFINET device.
Chapter 5 Diagnostics
Recommended
Correction
None.
Note: Alarm details are provided in the
Fault Extra Data
Consult Device manufacturer
documentation.
Note: Alarm details are provided in the
Fault Extra Data
Consult Device manufacturer
documentation.
Note: Alarm details are provided in the
Fault Extra Data
Consult Device manufacturer
documentation.
Note: Alarm details are provided in the
Fault Extra Data
Consult Device manufacturer
documentation.
Note: Alarm details are provided in the
Fault Extra Data
None.
Note: Alarm details are provided in the
Fault Extra Data
Consult Device manufacturer
documentation.
Note: Alarm details are provided in the
Fault Extra Data
None.
Note: Alarm details are provided in the
Fault Extra Data
Consult Device manufacturer
documentation.
Note: Alarm details are provided in the
Fault Extra Data
5