CHAPTER 5: SETTINGS
5.3.5.2 Serial ports
SETTINGS PRODUCT SETUP COMMUNICATIONS SERIAL PORTS
SERIAL PORTS
The front RS232 port applies to enhanced and standard front panels.
,
RS232 BAUD RATE
RS485 COM2 BAUD RATE
ports. The front panel RS232 port (USB port with graphical front panel) is intended for local use. The rear COM2 port is
RS485 and has settings for baud rate and parity. It is important that these parameters agree with the settings used on the
computer or other equipment that is connected to these ports. Any of these ports can be connected to a computer
running the EnerVista software, for example to download and upload setting files, view measured parameters, and
upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC, or computer
using the RS485 ports. If IEC 60870-103 is chosen as the protocol, valid baud rates are 9600 and 19200 bit/s, and valid
parity is Even.
RS485 COM2 RESPONSE MIN TIME
receiving data from a host. This feature allows operation with hosts that hold the RS485 transmitter active for some time
after each transmission.
5.3.5.3 Ethernet network topology
The D30 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP
address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND
operation performed between their respective IP address and mask produces a different result. Communication becomes
unpredictable when more than one port is configured to the same subnet.
Example 1
IP1/Mask1: 10.1.1.2/255.255.255.0 (where LAN 1 is 10.1.1.x/255.255.255.0)
IP2/Mask2: 10.2.1.2/255.255.255.0 (where LAN2 is 10.2.1.x/255.255.255.0)
IP3/Mask3: 10.3.1.2/255.255.255.0 (where LAN3 is 10.3.1.x/255.255.255.0)
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
DNP / IEC104
POINT LISTS
IEC 61850 PROTOCOL
WEB SERVER
HTTP PROTOCOL
TFTP PROTOCOL
IEC 60870-5-104
PROTOCOL
IEC103
PROTOCOL
USB 2.0 PORT
RS232 BAUD
RATE: 115200
RS485 COM2 BAUD
RATE: 19200
RS485 COM2 PARITY:
Even
RS485 COM2 RESPONSE
MIN TIME: 0 ms
, and
— The D30 is equipped with two independent serial communication
PARITY
— This setting specifies the minimum time before the rear RS485 port transmits after
See page 5-54
Access in EnerVista
See page 5-55
See page 5-99
See page 5-100
See page 5-100
See page 5-102
See page 5-107
Range: 19200, 115200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200 bit/s
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10
PRODUCT SETUP
5