CHAPTER 5: SETTINGS
Passwords are stored in text format. No encryption is applied.
In Device authentication mode, the Observer role does not have a password associated with it. In Server
authentication mode the Observer role requires a password.
If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry,
the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated password.
In CyberSentry, password encryption is not supported.
Session settings
SETTINGS PRODUCT SETUP SECURITY SESSION SETTINGS
SESSION
SETTINGS
— This setting specifies the number of failed authentications before the device blocks subsequent
SESSION LOCKOUT
authentication attempts for the lockout period. A value of zero means lockout is disabled.
— This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
SESSION LOCKOUT PERIOD
there is no lockout period.
Restore defaults
SETTINGS PRODUCT SETUP SECURITY RESTORE DEFAULTS
RESTORE DEFAULTS
— This setting is used to reset all the settings, communication, and security passwords. An
LOAD FACTORY DEFAULTS
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
Supervisory
SETTINGS PRODUCT SETUP SECURITY SUPERVISORY
SUPERVISORY
The Supervisory menu settings are available for Supervisor role only, or if the Supervisor role is disabled then for the
Administrator role only.
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
SESSION LOCKOUT:
3
SESSION LOCKOUT
PERIOD: 3 min
LOAD FACTORY
DEFAULTS: No
DEVICE
AUTHENTICATION: Yes
BYPASS ACCESS:
Disabled
LOCK RELAY:
Disabled
FACTORY SERVICE
MODE: Disabled
SELF TESTS
SUPERVISOR ROLE:
Disabled
SERIAL INACTIVITY
TIMEOUT: 1 min
Range: 0 to 99
Range: 0 to 9999 minutes
Range: Yes, No
Range: Yes, No
Range: Local, Remote, Local and Remote, Disabled,
Pushbuttons
Range: Enabled, Disabled
Range: Enabled, Disabled
See below
Range: Enabled, Disabled
Range: 1 to 9999 minutes
PRODUCT SETUP
5
5-21