PRODUCT DESCRIPTION
115.2 kbps. All serial ports use the Modbus RTU protocol. The IEC 60870-5-103 protocol is supported on the RS485
interface. IEC 60870-5-103, DNP, and Modbus cannot be enabled simultaneously on this interface. Also only one of the
DNP, IEC 60870-5-103, and IEC 60870-5-104 protocols can be enabled at any time on the relay. When the IEC 60870-5-103
protocol is chosen, the RS485 port has a fixed even parity and the baud rate can be either 9.6 kbps or 19.2 kbps. The
100Base-FX or 100Base-TX Ethernet interface provides fast, reliable communications in noisy environments. The Ethernet
port supports IEC 61850, Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access
to the relay via any standard web browser (D30 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet
port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when
2
purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
Settings and actual values can be accessed from the front panel or EnerVista software.
The D30 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
Table 2-1: ANSI device numbers and functions supported
Device
Function
number
21G
Ground Distance
21P
Phase Distance
25
Synchrocheck
27P
Phase Undervoltage
27X
Auxiliary Undervoltage
32N
Wattmetric Zero-Sequence Directional
49
Thermal Overload Protection
50DD
Current Disturbance Detector
50G
Ground Instantaneous Overcurrent
50N
Neutral Instantaneous Overcurrent
50P
Phase Instantaneous Overcurrent
50_2
Negative Sequence Instantaneous Overcurrent
51G
Ground Time Overcurrent
51N
Neutral Time Overcurrent
51P
Phase Time Overcurrent
2-2
CHAPTER 2: PRODUCT DESCRIPTION
Device
Function
number
51_2
Negative Sequence Time Overcurrent
52
AC Circuit Breaker
59N
Neutral Overvoltage
59P
Phase Overvoltage
59X
Auxiliary Overvoltage
59_2
Negative Sequence Overvoltage
67N
Neutral Directional Overcurrent
67P
Phase Directional Overcurrent
67_2
Negative Sequence Directional Overcurrent
68
Power Swing Blocking
78
Out-of-Step Tripping
79
Automatic Recloser
81R
Rate of change frequency
81U
Underfrequency
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL