Thank you for purchasing our product. If there is any question or request, please do not hesitate to contact the dealer. This manual is applicable to the following models: Series Models Description DS-K1101M MIFARE card reader (without keypad) DS-K1101MK MIFARE card reader (with a keypad) DS-K1101 Series...
Chapter 1 Preventive and Cautionary Tips To guarantee the card reader works properly, please read and obey the notes below. If the card reader is powered by the controller, the power supply distance is recommended to be no longer than 100m. If the distance is longer than 100m, you are advised to power the card reader by external 12V (range: -%10 ~ +%10) DC power supply, which is nonswitched and linear.
2.1 Front View The front view of DS-K1101 series card reader is shown below: Figure 2-1 DS-K1101MK/DS-K1101CK Figure 2-2 DS-K1101M/DS-K1101C The front view of DS-K1102 series card reader is shown below: Figure 2-3 DS-K1102MK/DS-K1102CK Figure 2-4 DS-K1102M/DS-K1102C The front view of DS-K1103 series card reader is shown below:...
Table 2-1 Description of Rear View Name Cable Interface of RS-485, Power, LED Control, etc. Buzzer Tamper-proof Module DIP Switch PSAM Card Slot (available for CPU card reader) 2.3 Side View The side view of card reader is shown below: Figure 2-10 Side View of DS-K1101 Series...
Figure 2-11 Side View of DS-K1102 Series Figure 2-12 Side View of DS-K1103 Series Chapter 3 Installation 3.1 Installing PSAM Card PSAM card slot is only available for CPU card reader. Insert the PSAM card into the slot according to the direction...
shown below. Figure 3-1 PSAM Card Slot 3.2 Introduction for DIP Switch The DIP switch module is shown below. The No. of DIP switch from left to right is 1 ~ 8. Figure 3-2 DIP Switch Module Table 3-1 Description of DIP Switch Icon Description Represent 1 in binary mode...
Table 3-2 Description of DIP Switch Description DIP Switch Status 1: 1 1 ~ 4 Address of RS-485 0: 0 Read card No. or file in card. 1: read card No; (Only available for CPU card 0: read file in card. reader.) Wiegand protocol or RS-485 1: Wiegand protocol;...
Color Description Orange Red LED Control (available for Wiegand Protocol) PWR (DC +12V) 3.4 Wiring Cables Purpose: Wire the cables between controller and card reader, thus to establish the communication between them. Steps for RS-485 communication mode: Set the DIP switch of No. 6 as 0. Set the DIP switch of No.
Page 12
Controller Card Reader Figure 3-4 Wiring for RS-485 Communication Mode Steps for Wiegand communication mode: Set the DIP switch of No. 6 as 1. Set the DIP switch of No. 5 and 7 for reading card mode and Wiegand protocol. For details, please refer to 3.2 Introduction for DIP Switch.
Controller Card Reader Figure 3-5 Wiring for Wiegand Communication Mode 3.5 Installing Card Reader Before you start: Set the DIP switch. For details, refer to 3.2 Introduction for DIP Switch. Steps:...
Fix the plate on the wall or other place. Connect the cables between controller and card reader. For details, refer to 3.4 Wiring Cables. Push the card reader to match the fixed plate. Fasten the screw to keep the components together. Chapter 4 Sound Prompt and Indicator After the card reader is powered on, LED status indicator will turn blue and blink for 1 time.
Page 15
Table 4-1 Description of Prompt Sound Sound Prompt Description RS-485 protocol: Pressing keys prompt; Swiping card prompt; Time out prompt for One beep pressing keys or swiping card. Wiegand protocol: Pressing keys prompt; Swiping card prompt. The operation of pressing keys or swiping Two rapid beeps card is valid.