Step
Connecting device to OneWireless network
1
If applicable, remove two T-15 TORX screws and cover lock clamp.
1.1
Using a screwdriver or other tool across the two tabs of the cover, unscrew and remove the
1.2
cover.
Using authentication device pointed at IR port, clear key and restart WCX transmitter.
1.3
After transmitter restarts, using authentication device, transmit key and connect transmitter.
1.4
Device will go through discovery mode, then secure itself to OneWireless network. After this
1.5
phase, transmitter will appear in Wireless Builder as an uncommissioned device.
Commissioning device in Wireless Builder
2
If this is not the first WCX Unit installed in this system, go to step 2.3, go to File->New-
2.1
>Type->Wireless Device, then find the path of the WCX DD Files.
Select the device that appears, then click OK, this creates a new device type in wireless builder.
2.2
In Wireless Builder: Offline Tab, right-click, go to New->Devices->(WCX_DD_FILE_NAME)
2.3
(this will create an offline configuration for the new device).
If device appears below "Unassigned" category, click and drag it into the wireless gateway.
2.4
Right-click on the newly created, offline device and go to Device Match.
2.5
In the device matching window, select both the offline device and uncommissioned device and
click "Match from Uncommissioned Device to Project Device". (This allows the factory settings
2.6
to automatically overwrite the DD files.)
After device has been matched, click OK.
2.7
Right click on the offline device and click "Load", Select all check boxes at the bottom of the
2.8
window, then click OK.
Now the device should be successfully loaded in Online mode and transmitting data.
2.9
ATTENTION
If the sensor or input linkage has been removed since the last successful calibration, and the
input shaft may have rotated past the potentiometer end points (where the slip clutch must slip),
then re-setting the device angle (steps 3-3.9) will be required (See Figure 2).
Setting WCX Sensor to valve (after device has been commissioned)
3
In the Offline window, double-click on the WCX transducer block (small rectangle with a T
3.1
inside), the parameters page will open.
In the Configuration tab, note the current update rate setting. If it is set to the default value of 30
seconds, change the "Period" to 5 seconds. This will greatly speed up the calibration. Click OK.
3.2
Note that a period of 1 second would update faster but would also introduce noise, which would
make calibration more difficult.
In the Offline window, right-click on the WCX Main block and click Load...
3.3
Ensure that "State to Load" is set to OOS and "Post Load State" is set to Normal, and both
boxes at the bottom of the window are checked. This will change the update rate on the sensor
3.4
and re-load it.
Revision 1
OneWireless XYR 6000 Wireless Valve Position Sensor User's Manual
1/15/09
Table 2 - Connecting, Commissioning, and Setting Angle
Action
3. 2BPreparation
3.6. Calibrating the Sensor
15