FLEXLOGIC
Operand type
RxGOOSE Boolean
Virtual Input
Virtual Output
The following table lists the operands available for the relay. The operands can be viewed online by entering the IP address
of the relay in a web browser and accessing the Device Information Menu.
Table 5-19: C70 FlexLogic operands
Operand type
CONTROL
PUSHBUTTONS
CYBERSENTRY
5
DIRECT DEVICES
DIRECT INPUT/
OUTPUT CHANNEL
MONITORING
ELEMENT:
Auxiliary overvoltage
ELEMENT: Automatic
voltage regulator
5-144
State
Example of format
On
RxGOOSE Boolean 1 On
On
Virt Ip 1 On
On
Virt Op 1 On
Operand syntax
CONTROL PUSHBTN 1 ON
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
ROLE ADMIN ACT
ROLE SUPERVISOR ACT
ROLE ENGINEER ACT
ROLE OPERATOR ACT
ROLE OBSERVER ACT
AUTHENTICATION FAIL
UNAUTH FW ATTEMPT
UNAUTH SETTING WRITE
DIRECT DEVICE 1On
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
DIRECT DEVICE 16Off
DIR IO CH1 CRC ALARM
DIR IO CH2 CRC ALARM
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
AUX OV1 PKP
AUX OV1 DPO
AUX OV1 OP
AUX OV2 to 3
AVR 1 CLOSE PKP
AVR 1 CLOSE OP
AVR 1 CLOSE DPO
AVR 1 OPEN PKP
AVR 1 OPEN OP
AVR 1 OPEN DPO
AVR 2 to 3
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Characteristics
[Input Is '1' (= ON) if...]
The RxGOOSE Boolean is presently in the ON state
The virtual input is presently in the ON state
The virtual output is presently in the set state (that is,
evaluation of the equation that produces this virtual output
results in a "1")
Operand description
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
Administrator role is active and is set to true when that is the case
Supervisor role is active and is set to true when that is the case
Engineer role is active and is set to true when that is the case
Operator role is active and is set to true when that is the case
Observer role is active and is set to true when that is the case
Operand set for Failed Authentication self-test and alarm
Operand set for firmware lock self-test and alarm
Operand set for settings lock self-test and alarm
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level
The rate of returned direct input/output messages on channel 1 exceeded
the user-specified level (ring configurations only)
The rate of returned direct input/output messages on channel 2 exceeded
the user-specified level (ring configurations only)
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has dropped out
Auxiliary overvoltage element has operated
Same set of operands as shown for AUX OV1
Automatic voltage regulator 1 picked up; close command pending
Automatic voltage regulator 1 issued a close command
Close command of automatic voltage regulator 1 dropped out
Automatic voltage regulator 1 picked up; open command pending
Automatic voltage regulator 1 issued an open command
Open command of automatic voltage regulator 1 dropped out
Same set of operands as shown for AVR 1