Product Description - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

C70 Capacitor Bank Protection and Control System
Chapter 2: Product description

Product description

This chapter outlines the product, order codes, and specifications.
2.1 Product description
The C70 Capacitor Bank Protection and Control System is part of the Universal Relay (UR) series of products. It is a
microprocessor-based relay for protection and control of small, medium, and large three-phase capacitor banks. The relay
can be ordered with up to three current transformer/voltage transformer (CT/VT) modules, allowing for flexible application
in variety of bank configurations.
The key protection functions cover grounded and ungrounded, single and parallel banks. Sensitive protection functions
support compensation for both external (system) unbalance and inherent unbalance of the capacitor bank itself. Both
voltage and current-based balance protection functions are available. Algorithms are developed to automatically select
compensation settings after repairs or other alternations of the bank.
The relay supports a variety of bank configurations through flexible configurations of its AC inputs, installed voltage and
current transformers, and resulting protection techniques.
The relay incorporates an automatic voltage regulator (AVR) responding to voltage, reactive power, or power factor. A
separate timer function initiates controls on a pre-defined time/date basis. These on-off type controls are meant to
automatically close or open the associated breaker. A supervisory function is provided to program the local/remote, auto/
manual functionality, temporary inhibit closing after tripping, and other auxiliary functions, such as operation counters.
A capacitor control element provides remote/local and auto/manual control regulation, trip/close interlocking, and seal-in.
A user-programmable time delay inhibits closing until after the bank discharges itself to a safe level.
The relay can also equipped with a serial 64/128 kbps direct input/output module for fast and reliable peer-to-peer
communication with other UR-series devices.
The C70 metering functions include true root mean square (RMS) and phasors for currents and voltages, current and
voltage harmonics and total harmonic distortion (THD), symmetrical components, frequency, power, power factor.
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of
storing up to 64 records with programmable trigger, content and sampling rate, and data logger acquisition of up to 16
channels, with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized
with an IRIG-B signal, using the Simple Network Time Protocol (SNTP) over the Ethernet port, or using the Precision Time
Protocol (PTP). This precise time stamping allows the sequence of events to be determined throughout the system. Events
can also be programmed (via FlexLogic™ equations) to trigger oscillography data capture that can be set to record the
measured parameters before and after the event for viewing on a computer. These tools significantly reduce
troubleshooting time and simplify report generation in the event of a system fault.