B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 26 of 51)
ADDR
REGISTER NAME
7541
Disconnect switch 1 name
7544
Disconnect switch 1 mode
7545
Disconnect switch 1 open
7546
Disconnect switch 1 block open
7547
Disconnect switch 1 close
B
7548
Disconnect switch 1 block close
7549
Disconnect switch 1 phase A / three-pole closed
754A
Disconnect switch 1 phase A / three-pole opened
754B
Disconnect switch 1 phase B closed
754C
Disconnect switch 1 phase B opened
754D
Disconnect switch 1 phase C closed
754E
Disconnect switch 1 phase C opened
754F
Disconnect switch 1 operate time
7550
Disconnect switch 1 alarm delay
7552
Disconnect switch 1 events
7553
Reserved (2 items)
7555
...Repeated for disconnect switch 2
756A
...Repeated for disconnect switch 3
757F
...Repeated for disconnect switch 4
7594
...Repeated for disconnect switch 5
75A9
...Repeated for disconnect switch 6
75BE
...Repeated for disconnect switch 7
75D3
...Repeated for disconnect switch 8
Thermal Overload Protecttion (Read/Write Settings)
7738
Thermal Protection 1 Function
7739
Thermal Protection 1 Source
773A
Thermal Protection 1 Base Current
773B
Thermal Protection 1 K Factor
773C
Thermal Protection 1 Trip Time Constant
773D
Thermal Protection 1 Reset Time Constant
773E
Thermal Protection 1 Minimum Reset Time
773F
Thermal Protection 1 Reset
7740
Thermal Protection 1 Block
7741
Thermal Protection 1 Target
7742
Thermal Protection 1 Events
7743
Reserved (2 items)
7745
Repeated for Thermal Protection 2
Broken conductor detection (Read/Write Settings)
7752
Broken Conductor 1 Function
7753
Broken Conductor 1 Source
7754
Broken Conductor 1 I2/I1 Ratio
7755
Broken Conductor 1 I1 Minimum
7756
Broken Conductor 1 I1 Maximum
7757
Broken Conductor 1 Pickup Delay
7758
Broken Conductor 1 Block
7759
Broken Conductor 1 Target
775A
Broken Conductor 1 Events
775B
Reserved (2 items)
775D
...Repeated for Broken Conductor 2
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60
User Programmable Pushbutton 1 Function
7B61
User Programmable Pushbutton 1 Top Line
7B6B
User Programmable Pushbutton 1 On Text
7B75
User Programmable Pushbutton 1 Off Text
B-34
RANGE
---
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
---
0 to 1
0 to 5
0.2 to 3
1 to 1.2
0 to 1000
0 to 1000
0 to 1000
0 to 65535
0 to 65535
0 to 2
0 to 1
---
0 to 1
0 to 5
20 to 100
0.05 to 1
0.05 to 5
0 to 65.535
0 to 65535
0 to 2
0 to 1
---
0 to 2
---
---
---
D30 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
s
0.001
F003
---
1
F102
---
---
---
---
1
F102
---
1
F167
pu
0.01
F001
---
0.05
F001
min.
1
F001
min.
1
F001
min.
1
F001
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F102
---
1
F167
%
0.1
F001
pu
0.01
F001
pu
0.01
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F109
---
---
F202
---
---
F202
---
---
F202
DEFAULT
"SW 1"
0 (3-Pole)
0
0
0
0
0
0
0
0
0
0
70
0
0 (Disabled)
---
0 (Disabled)
0 (SRC 1)
80
110
45
45
20
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
200
10
150
20000
0
0 (Self-reset)
0 (Disabled)
0
2 (Disabled)
(none)
(none)
(none)