Flexelements; Iec 61580 Goose Analog Values - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

6 ACTUAL VALUES

PATH: ACTUAL VALUES
METERING
 FLEXELEMENT 1
The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units.
Table 6–2: FLEXELEMENT™ BASE UNITS
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
dcmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)

PATH: ACTUAL VALUES
METERING
 IEC 61850
 GOOSE ANALOGS
MESSAGE
MESSAGE
MESSAGE
The D30 Line Distance Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
GE Multilin


FLEXELEMENTS

FLEXELEMENT 1(8)
FLEXELEMENT 1
OpSig: 0.000 pu
2
 cycle
BASE = 2000 kA
BASE = maximum value of the
DCMA INPUT MAX
under the +IN and –IN inputs.
f
= 1 Hz
BASE
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE

IEC 61850 GOOSE ANALOGS
ANALOG INPUT
1
0.000
ANALOG INPUT
2
0.000
ANALOG INPUT
3
0.000
ANALOG INPUT 32
0.000
D30 Line Distance Protection System
setting for the two transducers configured
 I
for the +IN and –IN inputs
BASE

6.3.6 IEC 61580 GOOSE ANALOG VALUES

6.3 METERING
6.3.5 FLEXELEMENTS™
6-17
6