5.7 CONTROL ELEMENTS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING
ELEMENTS
b) BREAKER ARCING CURRENT
5
PATH: SETTINGS
CONTROL ELEMENTS
BREAKER 1
ARCING CURRENT
There is one breaker arcing current element available per CT bank, with a minimum of two elements. This element calcu-
lates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current squared passing
through the breaker contacts as an arc. These per-phase values are added to accumulated totals for each phase and com-
pared to a programmed threshold value. When the threshold is exceeded in any phase, the relay can set an output operand
to "1". The accumulated value for each phase can be displayed as an actual value.
5-196
MONITORING ELEMENTS
BREAKER 1
ARCING CURRENT
BREAKER 2
MESSAGE
ARCING CURRENT
VT FUSE FAILURE 1
MESSAGE
VT FUSE FAILURE 2
MESSAGE
BROKEN CONDUCTOR 1
MESSAGE
BROKEN CONDUCTOR 2
MESSAGE
THERMAL OVERLOAD
MESSAGE
PROTECTION
MONITORING ELEMENTS
BKR 1 ARC AMP
FUNCTION: Disabled
BKR 1 ARC AMP
MESSAGE
SOURCE: SRC 1
BKR 1 ARC AMP INT-A:
MESSAGE
Off
BKR 1 ARC AMP INT-B:
MESSAGE
Off
BKR 1 ARC AMP INT-C:
MESSAGE
Off
BKR 1 ARC AMP
MESSAGE
DELAY:
0.000 s
BKR 1 ARC AMP LIMIT:
MESSAGE
1000 kA2-cyc
BKR 1 ARC AMP BLOCK:
MESSAGE
Off
BKR 1 ARC AMP
MESSAGE
TARGET: Self-reset
BKR 1 ARC AMP
MESSAGE
EVENTS: Disabled
D30 Line Distance Protection System
5.7.9 MONITORING ELEMENTS
See below.
See below.
See page 5–199.
See page 5–199.
See page 5–201.
See page 5–201.
See page 5–202.
BREAKER 1(2) ARCING CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.000 to 65.535 s in steps of 0.001
2
Range: 0 to 50000 kA
-cycle in steps of 1
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
GE Multilin