Goose Transmission - GE 869 Communications Manual

Motor protection system, control and management
Hide thumbs Also See for 869:
Table of Contents

Advertisement

THE IEC 61850 CONFIGURATOR

Goose Transmission

8-18
Buffered Report
3
2
1
The 869 relay has an IEC 61850 server and supports the GOOSE message scheme. A
maximum of three GOOSE control blocks can be added. The GOOSE Configuration has two
sections:
Transmission
Reception
GOOSE transmission configuration is described in this section.
Figure 8-13: Goose Transmission Screen
The GOOSE Transmission window has two screens.
GOOSE Tx control blocks: The user can add the required GOOSE control block.
Control Block Name: The first character in the value of this attribute must be a
letter (upper or lower case). The rest of the characters must be a number, a letter
(upper or lower case) or a "_". The maximum number of characters allowed is 32.
Description: The maximum number of characters allowed is 32.
GOOSE ID: The maximum number of characters allowed is 129.
Ethertype App ID: All characters must be numerical. The maximum number of
characters allowed is 4. IEC61850 Configurator allows characters limited to 0 to
9, A to F and it saves in the CID file the hexadecimal value (max FFFF).
Unbuffered Report
1
2
3
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 8: IEC 61850
Total Reports
4
4
4