Chapter 6: IEC 60870-5-104
FASTPATH:
FASTPATH:
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE

IEC 60870-5-104

The IEC 60870-5-104 communications protocol is supported on Ethernet ports 4 and 5
only. Setting changes become active after rebooting.
In 869 both DNP and IEC104 protocol can work at the same time, but the user has to
consider that there is only one point map. So, the two protocols use the same data
mapping, i.e., same point index and same point source.
The 869 supports up to two IEC104 client connections simultaneously.
Path:
Setpoints > Device > Communications > IEC 60870-5-104
IEC 60870-5-104
IEC104
CHANNELS
IEC104 COMMON
Message
ADDRESS OF ASDU:0
IEC104 NETWORK
Message
CLIENT ADDRESSES
IEC104 TCP
Message
PORTS
IEC104 CYCLIC DATA
Message
PERIOD: 60 s
IEC104 Obj Info
Message
Addr Binary: 1000
IEC104 Obj Info
Message
Addr Analog: 2000
IEC104 Obj Info
Message
Addr Counter: 3000
IEC104 Obj Info
Message
Addr Command: 4000
IEC104 Obj Info
Message
Analog Param: 5000
Range: see sub-menu below
Range: 0 to 65535 in steps of 1
Range: see sub-menu below
Range: see sub-menu below
Range: 0 to 65535 in steps of 1
Range: 0 to 16777215 in steps of 1
Range: 0 to 16777215 in steps of 1
Range: 0 to 16777215 in steps of 1
Range: 0 to 16777215 in steps of 1
Range: 0 to 16777215 in steps of 1
6-1