Usb - GE 869 Communications Manual

Motor protection system, control and management
Hide thumbs Also See for 869:
Table of Contents

Advertisement

CHAPTER 2: COMMUNICATION PORTS

USB

FASTPATH:
FASTPATH:
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
IP address:
192.168.0.1
Subnet Mask:
255.255.255.0
SSID:
same as entered on the PC (SSID provided with the 8-Series relay)
Broadcast
disabled
Security type:
WPA2-PSK (WPA2-Personal)
Encryption:
AES
Passphrase:
same as entered on the PC (Passphrase provided with the 8-Series relay)
DHCP enabled
range of 192.168.0.2 to 192.168.0.11
3.
If the 8-Series relay(s) are in range, they automatically connect to the configured
Access Point.
4.
Start EnerVista on a PC and use the Discover function, all relays within range appear
and are populated in Enervista for initial configuration and commissioning.
5.
Once the relay is configured, change the 8-Series relay default WiFi SSID and
Passphrase settings before the relay goes into service.
Figure 2-1: Example of WiFi Deployment
The USB parameters are as follows:
IP Address: 172.16.0.2
IP Mask: 255.255.255.0
IP Gateway: 172.16.0.1
Whenever the device is rebooted, the USB cable needs to be unplugged and plugged in
again for proper communication to be established over USB.
Connecting multiple 869 relays over USB to a single PC is not possible because in the case
of USB, the IP address of the device 172.16.0.2 is constant.
USB
2-5

Hide quick links: