Honeywell VISTA-128FBPN Installation And Setup Manual page 88

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide
ACTION CODES
30=Auto bypass – Zone list
31=Auto unbypass – Zone list
42=Enable Access Window for
Access group(s)
50=Off-Normal Reminder
PROMPT
01 Time Window ?
00:00
00:00
01
01 Active time ?
0
Days ? MTWTFSSH
Hit 0-8 x
x
Quit ?
1 = YES 0 = NO
0
6-10
EXPLANATION
Actions 30-31
If you selected actions 30-31, the prompt at the right appears. Enter the zone
list number that contains the zones to be bypassed or unbypassed.
Press [✳] to accept entry. The "Time Window ?" prompt appears.
Action 42
If you selected action 42, the prompt at the right appears. Enter the group
number to which the time window will apply.
Press [✳] to accept entry. The "Time Window ?" prompt appears.
Action 50
No action specifier is required for this action since the condition that this
occurs for are system-wide.
EXPLANATION
Enter the time window number (01-20) for which this timed event is to occur. As the number is keyed in, the
actual time that has been stored for the time window number is displayed.
Press [✳] to accept entry.
Enter the activation time from 1-10 (listed below). As the number is keyed in, the activation time is
displayed. The choices are:
1: Trigger at the start of the window.
2: Trigger at the end of the window.
3: Take effect only for the duration of the window.
4: Trigger at both the start and the end of the window. Example: coffee break buzzer.
5: Random trigger, up to 30 minutes, after the start of the window.
6: Random trigger, up to 30 minutes, after the end of the window.
7: Take effect only for the duration of the window, but random start and end the window up to 30 minutes.
Press [✳] to accept entry.
The system then asks for which days the event is to be activated.
Press 0 to toggle all days on or off; or press keys 1-8 to toggle the letter "x" under the day on or off (Monday
= 1, Holiday = H = 8).
When all entries have been made, the "TIMED EVENT #?" prompt is displayed again.
Repeat the procedure for each timed event for the installation.
Enter 0 at the "Quit ?" prompt to return to the main menu choices and continue programming. Enter 1 to quit
Scheduling Menu Mode.
ACTION SPECIFIER
01 ZONE LIST ?
ENTER 01-15
01
GROUP ? 12345678
HIT 0-8