Honeywell VISTA-128FBPN Installation And Setup Manual page 78

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-128FBPN Installation and Setup Guide
FIELD
TITLE and DATA ENTRIES
Enable Bell 2 & Auxiliary Relay
3*59
Chime Annunciation
0 = disable
1 = enable
Bell 2 & Auxiliary Relay Timeout
3*60
Enter 01-15 multiplied by 2 minutes.
00 = no timeout.
Auxiliary Relay Function
3*61
Selection
0 = trouble/supervisory
1 = alarm, silenced by User Code + OFF
2 = smoke detector reset
3 = battery save
4 = alarm, silenced by User Code + # + 67
Burglary Features on Partition 1
3*82
Enable
0 = disable
1 = enable
System Zone Bypass Inhibit
3*85
0 = prevent bypass
1 = allow only installer to bypass
2 = allow only installer and master codes to
bypass
5-16
EXPLANATION
This field has two entries, one for bell 2 and one for the auxiliary relay. If
enabled, the system produces chime annunciation on the output.
NOTE: Must be set to "0" if Bell 2 or Aux. Relay is used for Fire.
This field has two entries, one for bell 2 and one for the auxiliary relay.
Defines the length of time the output and the keypad's sounder will sound for
all audible alarms.
NOTE: Must be a minimum of 16 minutes for Commercial Burglary
installations and a minimum 6 minutes for UL Commercial Fire installations.
Select the condition that will trigger the auxiliary relay.
NOTES:
Select "4" for applications requiring independent resetting of the relay.
Smoke detector reset triggers the relay momentarily (approximately 6
seconds) on the second User Code + OFF entry.
Battery save is used to disconnect power from non-critical loads 4 hours after
AC loss.
If enabled, arming, test and chime modes can be used on partition 1.
NOTES:
These features are automatically enabled on all other partitions.
Must be set to "0" in Commercial Fire installations.
Select which codes, if any, can bypass fire zones and systems zones.
NOTES:
This applies to fire zones programmed with zone types 9, 16, 17, and 18 and
system zones 970-977.
The bypassing can only be done from partition 1.