Cross Zoning is designed so that a combination of two zones must be faulted within a 5-minute period of each other to cause
an alarm on either zone. This prevents momentary faults from one of the zones from causing an alarm condition. You can
select four "sets" of cross-zones (programmed in data fields 1*22, 1*23, 1*24, and 1*25), keeping in mind the following:
Both zones in each set must protect the same area.
Both zones in each set must be in the same partition.
Conditions That Affect Cross-Zone Operation
In the event of a continuous fault (lasting at least 5 minutes) on one of the paired zones, a fault on the second zone
causes an alarm immediately.
If one of the zones in a pair is bypassed or has a zone response type set to 0, the cross-zoning feature does not apply.
Do not cross-zone entry/exit zones with interior follower zones as this will produce unpredictable results.
If a relay is programmed to activate on a fault of one of the zones, the relay activates without the other zone being faulted.
If a relay is programmed to activate on an alarm or trouble, both zones must trip before the relay activates, and both
zones must restore for the relay to deactivate (if relay is programmed to deactivate on a Zone List Restore).
If the one of the zones trips and the second zone does not trip within the 5-minute period, an "error" message is
reported to the central station. The Contact ID event code is 378.
FIELD
TITLE and DATA ENTRIES
Cross Zoning Pair One
1*22
Enter 001-128
Enter 000,000 to disable
Cross Zoning Pair Two
1*23
Enter 001-128
Enter 000,000 to disable
Cross Zoning Pair Three
1*24
Enter 001-128
Enter 000,000 to disable
Cross Zoning Pair Four
1*25
Enter 001-128
Enter 000,000 to disable
Panic Button or Speedkey
1*26
For A, B, C keys:
00 = panic function
01-32 = macro number
For D key:
00 = to select a macro to execute when key
is pressed
01-32 = macro number
RF Transmitter Low Battery
1*28
Sound
0 = disarmed state only
1 = both armed and disarmed states
RF Transmitter Low Battery
1*29
Reporting
0 = disable
1 = enable
RF Receiver Supervision Check-
1*30
in Interval
Enter 02-15 times 2 hours (4-30 hours).
00 = disable receiver supervision.
EXPLANATION
Select the first pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to "000,000 "for Commercial Fire and Burglary installations.
Select the second pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to "000,000" for Commercial Fire and Burglary installations.
Select the third pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to "000,000" for Commercial Fire and Burglary installations.
Select the fourth pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to "000,000" for Commercial Fire and Burglary installations.
Select for the A, B, and C keys whether the system performs a panic or a
speedkey function when the key is pressed.
Select for the D key whether the system performs a specific macro or if the
user will select a macro when the key is pressed.
Select when the RF transmitter low-battery condition should display and
audible beep annunciate on the keypad.
Must be 1 for Commercial Fire and UL Commercial Burglary installations.
If enabled, the system sends a Trouble message for RF transmitter low-
battery condition to the central station.
NOTE: The Trouble message will be sent for a transmitter supervision failure,
independent of this selection.
Must be 1 for Commercial Fire and UL Commercial Burglary installations.
Select the check-in monitoring interval for the RF receiver(s).
Failure of a receiver to receive any RF signal within the time entered results in
the activation of the response type programmed for zone 990 for the first
receiver and zone 988 for the second receiver and their related
communication reports.
Maximum is 2 (4 hr) for Commercial Fire and UL Commercial Burglary
installations.