Honeywell VISTA-128FBPN Installation And Setup Manual page 69

Commercial fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

FIELD
TITLE and DATA ENTRIES
Zone Type Restores for Zone
*79
Types 1-8
0 = disable
1 = enable
Zone Type Restores for Zone
*80
Types 9, 10 & 14
0 = disable
1 = enable
First Test Report Time
*83
Enter 00-07the for day (01 = Monday)
Enter 00-23 for the hour
Enter 00-59 for the minutes
Swinger Suppression (partition-
*84
specific)
01= 1 alarm
02= 2 alarms
Enter 00 for unlimited reports
Enable Dialer Reports for Panics
*85
& Duress (partition-specific)
0 = disable
1 = enable
Entry Warning (partition-specific)
*87
0 = 3 short beeps
1 = slow continuous beeps
Abort Window (partition-specific)
*88
1 = 15 seconds
2 = 30 seconds
3 = 45 seconds
Alarm Restore Report Timing
*89
0 = Restore is sent when zone is restored or
at disarming, whichever occurs first.
1 = Restore is sent at disarming whether
zone is restored or not, or at bell timeout, but
only if restored.
2 = Restore is sent at disarming, whether the
zone is restored or not.
Secondary Subscriber Account
*90
Number (partition-specific)
Enter 00-09; B-F (11-15)
EXPLANATION
This field has eight entries, one for each zone type. Select the zone types that
will send Restore reports.
This field has three entries, one for each zone type. Select the zone types that
will send Restore reports.
Restores must be set to "1" for Commercial Fire installations.
Enter the day and time that the first Test report shall be transmitted. Enter 00
in all locations if the Test report is to be sent immediately upon exiting. Enter
00 in the day location if the report is to be sent at the next occurrence of the
time that is set.
This feature limits the number of times a non-fire zone locally annunciates and
transmits an alarm report to the central station, if a report is programmed, per
armed period.
A prompt has been added to Zone Programming for each zone to
enable/disable this option (Swinger Suppression Enable) with choices 0 = no
suppression; 1 = yes, suppress alarms according to field *88 selection.
NOTE: Fire zones are exempt from this requirement.
Must be set to "00" for Commercial Fire and Burglary installations.
This field has four entries as follows: Zone 995, 996, 999, Duress Enable for
each partition that the panics and duress reporting is desired.
NOTE: Non-zero report code must be assigned to zone 992 (duress) to
enable Duress reporting.
If you enable any of the panics to report, make sure field *22 is programmed
correctly for each partition.
Select the type of warning for the entry delay period.
The Abort Window exists for all non-fire zones. All non-fire alarm reports are
NOT transmitted to the central station, if the code sequence is entered
within the Abort Window.
Otherwise, non-fire alarm reports are transmitted to the central station, if
programmed to do so, if the code sequence is not entered during the
Abort Window.
A prompt has been added to Zone Programming for each zone to
enable/disable this option (Abort Window Enable) with choices 0 = no abort
window, 1 = yes, use abort window according to field *88 selection. Each
non-fire zone MUST be programmed with a 0 for UL installations.
This field must be set to (2) for SIA installations.
Select the time when restore reports are sent after an alarm.
This field applies only to Burglary zone types. It does not apply to Fire or
Panic zone types.
Must be set to "2" for Commercial Burglary installations.
Enter a 3- or 4-digit (depending on report format) primary subscriber account
number. Each number requires a 2-digit entry so as to allow entry of
hexadecimal digits (B-F). If a 3-digit account number is to be used, enter data
only in the first three locations, and enter * in the fourth location.
NOTE: This field must be programmed if a secondary phone number is used
(field *34). This account number can be the same as the primary account
number.
Section 5 – Data Field Descriptions
5-7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-128fbpVista-250fbp

Table of Contents