PROMPTS
nd
2
City ID
14
(??)_
nd
2
CS ID
15
(??)_
nd
2
Sub ID
16
(????)_
Device Address
17
(03)_
Enable DW Y/N
18
(N)_
Direct Wire Addr
19
(28)_
Supervision
20
(24 Hours)_
GSM Rollover Y/N
21
(Y)_
GSM 24Hr Tst Y/N
22
(N)_
3-4
ENTRY
OPTIONS
[01-99]
[01-FE]
[0001-9999]
[01-30]
[Y], [N]
[01-30]
• 30 Day
• 24 Hour
• None
[Y] , [N]
[Y], [N]
DESCRIPTION
Enter the 2-digit secondary city ID, 01-99 (decimal).
Enter the 2-digit second central station's ID number,
01-FE (HEX).
Enter the 4-digit subscriber account number for the
second central station, 0001-9999.
In ECP mode, the 7845i-GSM communicates with the
panel as a Long Range Radio (LRR) device. Enter the
appropriate ECP device address. For VISTA-10 and
VISTA-20 series control panels, use address 03. For
other controls, see the control panel's Installation and
Setup Guide.
NOTES:
1. When programming the control, enable the LRR
output.
2. The device address must be unique from the
"Direct Wire Addr" entered in Prompt 19.
Applies only to VISTA-128BP/250BP and FBP Series
controls.
Enables Direct Wire Downloading over IP.
If [N,] skip to Prompt 20: "Supervision."
When using Direct Wire downloading, the 7845i-GSM
communicates with the panel as an alpha keypad to
initiate the direct wire download session. Enter the
appropriate device address.
NOTES:
1. This address must also be programmed as an
alpha keypad in the control panel (Device
Programming Mode). DO NOT connect an actual
keypad (or any other device) assigned to this
address.
2. This address must be unique from the "Device
Address" entered in Prompt 17.
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies the
central station that a communication failure has
occurred. (If the supervision period is changed after
registration, you must re-register the module.)
Press the [space] key to scroll through choices.
UL NOTE: Must be 24 hours.
If enabled, all messages (including AlarmNet network
supervisory messages) are sent over the GSM network
in the event of an Internet failure.
If disabled, all messages (except AlarmNet network
supervisory messages) are sent automatically over the
GSM network in the event of an Internet failure.
If enabled, the 7845i-GSM sends a message once a day
to verify radio operation. A "secondary communication
path loss" message is generated if the message is not
successfully delivered.