SOFTWARE INTERFACE
Advanced EnerVista 8 Series Setup Software Features
FlexCurve Editor
3–38
The FlexCurve Editor is designed to allow the user to graphically view and edit the
FlexCurve. The FlexCurve Editor screen is shown as follows:
•
The Operate Curves are displayed, which can be edited by dragging the tips of the
curves
•
A Base curve can be plotted for reference, to customize the operating curve. The Blue
colored curve in the picture is a reference curve. It can be Extremely Inverse, Definite
Time, etc.
•
The Trip (Reset and Operate) Times in the tables and curves work interactively i.e.,
changing the table value affects the curve shape and vice versa.
•
The user can save Configured Trip Times.
•
The user can export Configured Trip Times to a CSV file
•
The user can load Trip Times from a CSV File
•
The screen above shows the model followed by 850 for viewing FlexCurves. Select
Initialize to copy the trip times from the selected curve to the FlexCurve.
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INTERFACES