2. Click the Calibration button to display the CALIBRATION menu.
3. In the Apply Values group, click Set LRV. The following message will be displayed;
a. The value of the input shown in the Set LRV box above updates only when the popup
is called up.
b. To update the input value, click No, and then click the Set LRV button in the
CALIBRATION display.
4. Set the LRV as follows:
a. While observing the PV value at the physical process element (using a sight glass, for
example), adjust it to the desired minimum (0 %) level, and then click Set LRV.
b. If the displayed value is satisfactory, click Yes to copy the Input Value to the LRV in
the Transmitter. If not, click NO and repeat this step.
Page 66
ST 700 Series HART/DE Option User's Manual
Revision 4.0