Online/Device
Setup/Calibration
Revision 4.0
PV Damping
SV Units
Write Protect
PV Levels
Calibration Methods
Filter Performance
Selection
Correct URV
Records
Correct LRV
Records
Zero Trim Records
Reset Correct
Records
ST 700 Series HART/DE Option User's Manual
Enter a value for damping of the device output.
Entries may be any value from 0.00 to 32.00
seconds.
Click the relevant unit for measurement of the
Secondary Variable (Meter Body Temperature).
The available measurements are:
o
o
o
C ,
F,
R, Kelvin
Displays the current configuration of the write
protect function. Write Protect is "Enabled" if either
the write protect jumper on the electronics board is
in the ON position or the firmware write protect has
been enabled.
Displays a graphic representation of all PV ranges
and limits for the ST 700 Pressure Transmitter
The following calibration methods are available:
Apply Values: Performs a Set LRV and/or
Set URV to configure the LRV/URV to
applied inputs.
Enter Values: Enter desired LRV and URV
value to configure the desired operating
range. Valid entries are from LTL to UTL
(lower/upper transducer limits).
D/A Trim: Perform an analog output
calibration at 4.00 and 20.00mA (0% and
100% output).
Zero Trim: Perform an input calibration
correction by applying process input at zero.
LRV Correct: Perform an input calibration
correction by applying process input at the
configured LRV level.
URV Correct: Perform an input calibration
correction by applying process input at the
configured URV level.
Reset Corrects: Clear all user calibration
adjustments.
Configure the desired performance for the Output
Speed of Response Filter. Select from:
Standard SOR : Excellent speed of
response to input changes with optimal noise
performance
Fast SOR: Fastest speed of response to
input changes
Displays the time and date history records for the last
three URV Correct calibrations.
Displays the time and date history records for the last
three LRV Correct calibrations.
Displays the time and date history records for the last
three Zero Trim calibrations.
Displays the time and date history records for the last
three times Reset Corrects was issued.