Honeywell ST 700 User Manual page 151

Smartline series
Hide thumbs Also See for ST 700:
Table of Contents

Advertisement

Online/Device
Setup/Diagnostics
Online/Device
Setup/Services
Revision 4.0
Displays Advanced Diagnostics details for tracking basic
device operation. For more detailed information on
Advanced Diagnostics, refer to the HART Advanced
Diagnostics section in this Manual. Diagnostic
information includes:
Adv Diagnostics
Displays a history of the last five configuration
Config History
parameters that have been changed.
Displays a picture of the Electronics module to
Write Protection
demonstrate how to connect the hardware write protect
jumper.
Displays the current configuration of the write protect
function. Write Protect is Yes (enabled) if either the
Write Protect
write protect jumper on the electronics board is in the
ON position or the firmware write protect has been
enabled.
Configure the firmware write protect option.
Write Protect options are:
Write Protect
On/Off
A 4-digit password is required to change the Write
Protect option from Enabled to Disabled to allow
configuration changes.
The default password is 0000, and can be re-configured
by the user.
Change the write protect password to a new 4-digit
Change Password
code.
This option causes a Master Reset of the transmitter,
Master Reset
which is the equivalent to power cycling the device.
This function enables the user to test the Analog
Output measurement at any value over the full
operational range. Click a current value to apply to the
Loop Test
output and verify the measured current on the loop with
a calibrated meter.
Note: This function is only available when Loop mA
(Loop Current mode) is Enabled.
Click the Lock state for access by HART configuration
tools.
If Yes is selected to lock the device, also click" or No to
choose whether or not the lock is "permanent." If the
Lock/Unlock
Device
lock is not permanent, it will be cleared on power cycle
or Master Reset of the device.
If Yes is selected to unlock the device, the lock state
will be cleared.
ST 700 Series HART/DE Option User's Manual
Installation and Device Life details
PV Tracking details
SV Tracking details
TV Tracking details
ET Tracking details
Operating Voltage details
AVDD Tracking details
Sensor CPU Temp. Tracking details
Power Up Diagnostics details
Enable: enables the firmware write protect
option (changes in configuration parameters
will not be permitted).
Disable: disables the firmware write protect
option (requires a password).
Page 137