3.4 Copy Project to SD Card

3.5 Proficy Machine Edition Project Update

26
GFK-2847R
For public disclosure
The custom utility Copy Project to SD Card transfers Proficy Machine Edition View and
Control projects between compatible QuickPanel
Caution
➢ ➢ To copy a Proficy Machine Edition project to an SD card
1.
Verify that there is a blank SD card in the SD card port.
Double tap the Copy Project to SD Card icon on the desktop.
2.
From the Copy Project Query confirmation window, tap Yes.
3.
Caution
Update a Proficy Machine Edition (PME) application that is currently stored on the
QuickPanel
+
unit with a revision stored on a flash device, such as an SD card.
➢ ➢ To update a Machine Edition project
1.
Insert the flash device containing an upgraded version of the Proficy Machine Edition
project into the appropriate port.
2.
Restart the unit.
Note Depending on set options, the update may or may not be enabled, or may
update automatically. If there is more than one flash device with a valid project copy
present, a Select Media confirmation window displays, prompting you to choose with
which flash device to update Select the device from the list and click OK to continue.
When a valid project is found on the flash device, you will be prompted to install the
project or skip it. Tap OK to install or Cancel to skip the installation, and continue
to restart. If an invalid project is found, an error message displays. This window must
be closed before the unit will restart.
3.
Remove the flash device from the port.
+
units using SD cards.
Before disconnecting power, verify that the copy or
update operation is complete (no busy message or
wait cursor).
Copying a project while Proficy Machine Edition
runtimes are active may cause an incomplete copy to
be created if the runtimes are also writing to files in
the project folders. If the utility detects this
situation, it will notify you to stop the runtimes
before making the backup. You will not be able to
create a backup while the runtimes are writing files.