Lad Cancel By Setting Acc/Dec; Analog Input O/Oi Monitor(Always Enable); Pulse Train Input Monitor (Always Enable) - Hitachi WJ200-001S Instruction Manual

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Ver.3− − − − 4

LAD cancel by setting ACC/DEC

T he lower limit of the acceleration/deceleration time's set range, such as F002/F003,is 0.00.
Object parameter:
F002, F202, F003, F203, A092, A292, A093, A293
W hen the applied acceleration/deceleration time is 0.00[s], the inverter operate similar to LAC ON.
T he inverter sets the instruction frequency into the output frequency whenever the driving instruction FW/RV
is ON and LAC is ON. And, the inverter sets 0Hz into the output frequency when the driving instruction
FW/RV is OFF.
Analog input O/OI monitor (always active)
A bout "Analog input O", monitor display (d130) newly added. Its data range is 0-1023 and always active.
About "Analog input OI", monitor display (d131) newly added. Its data range is 0-1023 and always active.
Pulse train input monitor (always active)
T he monitor of the pulse train input to the terminal EA is always valid and is independent of any parameter
setting. That is displayed in the menu "d133" newly installed. That is the value after the Full Scale (P055)
conversion and the filter processing with the time constant (P056), and before bias(P057) processing. The unit of
the data is [0.01% (Full Scale (P055) standard)].The data can be read from Modbus and EzSQ.
Pulse input
P055 (1.0~32.0 kHz)
P056 (0.01~2.00s)
kHz
%
1
÷
1+sT
d133(0.00 ~ 100.00 [%])
Bias / limit / cut
100%
P058
P057
P059
0%
%
Hz
Frequency
×
command
A004

Advertisement

Table of Contents

Troubleshooting