Periodical check

Since the drive stops even one of the GS1 or GS2 is interrupted, it is to be reconfirmed
that there is not faiure in the path of GS1 and GS2 periodically. Period of this
maintenance is once per year, and the method to make sure GS1 and GS2 in
combination with EDM signal is as described below.
Terminal
GS1
GS2
EDM
(output)

Precautions

1. To assure, that the Safe Disable function appropriately fulfills the safety
requirements of the application, a throughout risk assessment for the whole safety
system has to be carried out.
2. If EDM signal is not utilized in the system as a reconfirmation of redundancy
between GS1 and GS2, PL of drive is downgraded to PL=c.
3. The Safe Disable function does not cut the power supply to the drive and does not
provide electrical isolation. Before any installation or maintenance work is done,
the drives power supply must be switched off.
4. The wiring distance for the Safe Disable inputs should be shorter than 30 m.
5. The time from opening the Safe Disable input until the drive output is switched off
is less than 10 ms.
6. When two or more inverters are connected to common GS1 and GS2 wiring, please
be sure to put the diode as instructed in page 4-14, otherwise the drive may start to
work even in the safety mode.
current OFF
current ON
current OFF
current OFF
conducted
not conducted
forbidden
forbidden
Status
current OFF
current ON
not conducted
forbidden
current ON
current ON
not conducted
Allowed