In inverter applications it is useful to monitor the
inverter operation from a remote location or from the
front panel of an inverter enclosure. In some cases,
this requires only a panel-mounted volt meter. In
other cases, a controller such as a PLC may provide
the inverter's frequency command, and require
inverter feedback data (such as output frequency or
output current) to confirm actual operation. The
analog output terminal [AM] serves these purposes.
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as
analog GND reference. The [AM] can output inverter frequency or current output value.
Note that the voltage range is 0 to +10V (positive-going only), regardless of forward or
reverse motor rotation. Use
Func.


Code
Description

Inverter output frequency

Inverter output current

Inverter output torque

Digital output freqnency

Inverter output goltage

Inverter input power

Electronic Thermal Load

LAD frequency

Digital current monitor

Cooling fin temperature

General purpose

Pulse train

Option
to configure terminal [AM] as indicated below.
AM H
O OI L
Analog
+
A GND
Voltage
Output
10VDC
full scale,
2mA max
See I/O specs on page4-6
-