Program
Pressing the THRESHOLD SETUP soft key at the Module Point Programming screen will display
this screen.
Soft Keys
T H R E S H O L D N U M B E R :
T H R E S H O L D V A L U E :
type specified on the FMM-4-20 Device Setup Screen)
E V E N T :
EVENT,TROUBLE, FIRE, SUPERVISORY, SECURITY, NONFIRE, CRITICAL PROCESS.
T R O U B L E T Y P E :
INHIBIT. Device Inhibit will generate a trouble when the FMM-4-20 is in a self-calibration state.
E V E N T T R I G G E R :
SAME LEVEL.
T R A C K I N G / L A T C H I N G :
one threshold has been programmed as latching, the first threshold reached will be the one that is latched.
A C C E P T :
54
M O D U L E P O I N T P R O G R A M M I N G
T H R E S H O L D N U M B E R 1
T H R E S H O L D V A L U E : 5 0 0 . 2 5 P P M
E V E N T T R O U B L E
T R O U B L E T Y P E : T R O U B L E 1
E V E N T T R I G G E R : L O W E R L E V E L
Figure 3.43 FMM-4-20 Threshold Setup Screen
Enter the threshold number (1 - 5) that will be described in this screen.
Enter the value for this threshold. (Threshold value is represented in the unit
Select the event type that will generate when this threshold is reached. Selections are NO
Select a trouble type for this threshold: TROUBLE 1, TROUBLE 2 or DEVICE
Select LOWER LEVEL (values are falling), UPPER LEVEL (levels are rising), or
Select TRACKING or LATCHING for the threshold trouble. If more than
Press to save screen entries.
L 0 3 M 1 5 0
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Point Program
L A T C H I N G
A C C E P T
B A C K