Honeywell nfs2-3030 Programming Manual page 23

Fire alarm control panel
Hide thumbs Also See for nfs2-3030:
Table of Contents

Advertisement

Panel Program
DCC PARTICIPATION: Press this key to program the panel for DCC (Display and Control Center)
participation. This network function ensures that one location at a time is in command of the
Acknowledge, System Reset, Signal Silence and Drill functions. Default: NO
CAUTION:
!
ON SYSTEMS UTILIZING THE DCC FUNCTION, ALL LOCATIONS THAT CAN PARTICIPATE IN
DCC SHOULD BE SET TO YES.
RAPID ALL CALL: Set YES to invoke Rapid All Call for XP Series transponder modules. For use
when retrofitting an AM-2020/AFP-1010 system that has XPP modules used for audio operation.
This setting causes these modules to activate more quickly. Rapid All Call is used with the
"Speaker" type code. Default:NO
DEFAULT SETTINGS: Press this soft key to activate default settings for the following:
REGIONAL SETTINGS: Press this soft key to proceed to the Regional Settings screen. Press the
soft key to scroll through the selections. The default is that there are no special regional settings.
Other settings are explained in Appendix I, "Regional Settings".
MORE: Press this key to progress to the third Panel Settings screen.
NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Program Setting for:
Local Control
Piezo
Proprietary Supervising Station
Event Ordering
Display Address
LCM Local Mode
DCC Participation
Power Management
Rapid All Call
Table 3.2 Default Settings
P A N E L S E T T I N G S
S O U N D E R B A S E S E T U P
N E T W O R K D I S P L A Y M O D E : O N
D R I L L M O D E : C U S T O M
Figure 3.8 Panel Settings (3) Screen
Default:
YES
ON
NO
USA
YES
NO
NO
OFF
NO
M O R E
A C C E P T
B A C K
Program
23