Appendix A: Wire Requirements

Connecting external system accessories to the main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, gauge and run length for each cir-
cuit. The following table lists NAC wiring requirements for the HPF24S6 and HPF24S8 Field
Charger Power Supply.
Max.
allowable
NAC Load
total loop
(Amps)
resistance
(ohms)
0.25
6.00
0.5
3.00
0.75
2.00
1.0
1.50
1.25
1.20
1.5
1.00
1.75
0.86
2.0
0.75
2.25
0.67
2.5
0.60
2.75
0.55
3.0
0.50
Table A.1 NAC Wiring Requirements for Power Supply
NOTE: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.
HPF24S Series Power Supplies — P/N 52751:E1 4/14/2011
CLASS-B
Max. allowable wire pair lenth
(feet)
AWG 12
AWG 14
AWG 16
solid
solid
solid
1554
977
777
489
518
326
389
244
311
195
259
163
222
140
194
122
173
109
155
98
141
89
130
81
Max. allowable wire pair length
AWG 18
AWG 12
solid
solid
613
386
777
307
193
389
204
129
259
153
97
194
123
77
155
102
64
130
88
55
111
77
48
97
68
43
86
61
39
78
56
35
71
51
32
65
CLASS-A
(feet)
AWG 14
AWG 16
AWG 18
solid
solid
solid
489
307
244
153
163
102
122
77
98
61
81
51
70
44
61
38
54
34
49
31
44
28
41
26
193
97
64
48
39
32
28
24
21
19
18
16