Honeywell HPF24S6 Installation Manual page 11

Field charger/power supply
Hide thumbs Also See for HPF24S6:
Table of Contents

Advertisement

Specifications
– Maximum for any one circuit - 3.0 amps
– Maximum total continuous current for all output:
HPF24S6 - 4.0 amps
HPF24S8 - 6.0 amps
– Maximum total short term current (one hour maximum) for all outputs:
HPF24S6 - 6.0 amps
HPF24S8 - 8.0 amps
Output Circuit Types:
– Four Style Y NACs (require 4.7 KEnd-of-Line Resistors) or
Style Z NACs using the optional ZNAC-4 Class A converter module
– Four resettable or nonresettable 24 VDC power outputs
Refer to the HPP Device Compatibility Document #54399 for listed compatible devices.
For wiring requirements, refer to "Wire Requirements" on page 43.
Trouble Relay Contact Rating - TB5
Fail-safe Form-C relay (normally energized, transfers with loss of power)
5.0 amps @ 24 VDC or 5.0 amps @ 30 VAC
Secondary Power (battery) Charging Circuit - JP4
Supervised, nonpower-limited
Supports lead acid type batteries only
Float Charge Voltage: 27.6 VDC
Maximum Charge Current: 1.5 A
Battery fuse (F1) 15A, 32V (Canadian version is nonreplaceable 12A, 32V)
Maximum Battery Capacity: 18.0 AH
Minimum Battery Capacity: 7.0 AH
Power supply draws maximum standby current of 65 mA from batteries
Auxiliary Special Application Power Output - TB4 Terminals 9 (+) & 10 (-)
Special application power
Power-limited, nonsupervised
Voltage Rating: 24 VDC
Current:
– 170 mA maximum with internal 7.0 Amp Hour batteries
HPF24S Series Power Supplies — P/N 52751:E1 4/14/2011
OR
System Overview
11