Honeywell HPF24S6 Installation Manual page 12

Field charger/power supply
Hide thumbs Also See for HPF24S6:
Table of Contents

Advertisement

System Overview
– 500 mA maximum with external 18.0 Amp Hour batteries
Nonpower-limited
To Transformer #1
To Transformer #2
Supervised,
Nonpower-limited
Earth
AC Neutral
AC Hot
EARTH NEUT HOT
TB1
J2
J1
F1
- +
JP4
BATTERY
JP4 Supervised
+ Battery
- Battery
18 AH, 24 VDC
Nonpower-
F1
limited
Battery Fuse
15A, 32V
(Canadian version
is nonreplaceable
12 A, 32V)
NOTE: Cutting Ground Fault jumper JP1 voids UL/NFPA Style/Class identifications for circuits
unless Ground Faults are being monitored by an FACP connected to the power supply. Cut
jumper JP1 only if a panel connected to the power supply is monitoring for Ground Faults or with
the approval of AHJ (Authority Having Jurisdiction).
12
Power-limited, Supervised,
Special Application
in NAC Mode
NAC/Out 1 +
NAC/Out 1 -
NAC/Out 2 +
NAC/Out 2 -
NAC/Out 3 +
NAC/Out 3 -
NAC/Out 4 +
NAC/Out 4 -
GND
NAC
AC/
AC
FLT
BATT
TRBL
CHGR
SW1
LEDs
Charger Trouble/AC Loss (yellow)
NAC Trouble (yellow)
Battery Trouble (yellow)
Ground Fault (yellow)
AC Power (green)
Figure 1.1 HPF24S Board Layout
OUT4
OUT3
OUT2
OUT1
- NAC4 +
- NAC3 +
- NAC2 +
- NAC1 +
TB2
8
7
6
5
4
3
2
1
J3
Auxiliary Output
AUX -
500 mA Special
Application Power*
AUX +
IN2-
IN2+
OUT1-
OUT1+
IN1-
IN1+
SYNC IN -
SYNC IN +
O N
1 2 3 4 5 6 7 8
TB4
SW1
Programming
DIP Switches
(change switch
settings only
when all power
(AC & DC) is
removed)
HPF24S Series Power Supplies — P/N 52751:E1 4/14/2011
Specifications
Trouble Relay
Form-C Fail-safe
Nonsupervised
(shown energized)
Normally Open
Normally Closed
Common
AUX TBL
NO
NC
COM
TB5
JP1 Ground Fault
3
2
1
Detection
(cut to disable)
see Note at
bottom of the
page.
JP1
J3
ZNAC-4 Connector
JP2
JP2 & JP3
JP3
Coded/Noncoded
Input Selection
10
- Aux. Common
9
+ Aux. 24 VDC*
8
- Control Input 2
7
+ Control Input 2
6
- Out Common
5
+ Out/Trouble Contact
4
- Control Input 1
3
+ Control Input 1
2
- Sync Input
1
+ Sync Input
*Note: Auxiliary Power
Output is power-limited
but not supervised

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpf24s6cHpf24s8cHpf24s8Hpf24s6eHpf24s8e