Honeywell HPF24S6 Installation Manual page 32

Field charger/power supply
Hide thumbs Also See for HPF24S6:
Table of Contents

Advertisement

Applications
power supply output circuits 1 & 2 to turn on. Control Input #2 (TB4, Terminals 7 & 8) is con-
nected to an FACP Notification Appliance Circuit which is used to activate the power supply's tem-
poral output circuits 3 & 4.
Internal Trouble Contact
HPF24S
1 2 3 4 5 6 7 8 9 10
End-of-Line
Resistor supplied
with Control Module
T11
T11
T1
T10
T10
T1
T2
T9
T9
T2
T3
T8
T8
T3
T4
T7
T7
T4
T5
T6
T6
T5
Control Module*
*If the SLC device does not match the one in this
figure, refer to the SLC manual wiring conversion
charts for legacy and newer versions of the modules.
32
Note: All NACs are supervised and power-limited
ELR not required for
-
+
Style Z (Class A) NAC
-
+
Bells
-
+
TB2
-
-
8
7
+
+
Style Z (Class A)
ZNAC-4
Option Module
SLC
NAC
(steady,
FACP
no sync)
Figure 5.3 Split Temporal Mode Application
Use listed ELR
(4.7K) to
terminate Style Y
(Class B) NAC
TB2
8
7
Style Y (Class B)
8
Temporal Bell Circuit 4
7
6
Temporal Bell Circuit 3
5
4
Horn/Strobe Circuit 2
3
2
Horn/Strobe Circuit 1
1
3
2
1
FACP NAC
SW1 Switch Settings
End-of-Line
1 & 2 = sync (any setting but
Resistor
OFF/OFF)
3 = OFF (master)
4 = OFF (no AC Fail reporting delay)
5 = ON
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
HPF24S Series Power Supplies — P/N 52751:E1 4/14/2011
Split Temporal Mode of Operation
-
+
-
+
Bells
-
+
-
+
Split Temporal

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpf24s6cHpf24s8cHpf24s8Hpf24s6eHpf24s8e

Table of Contents