Huawei SmartDC V100R021C10 User Manual page 57

Data center controller
Hide thumbs Also See for SmartDC V100R021C10:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Appearance
Figure 3-20 Smart module actuator
(1) 48 V DC power
input port
(5) DIP switch
(9) Fuse
(13) Wiegand ports
Specifications
Table 3-39 Indicators
Item
Power Input
Power output
LAN port
Issue 04 (2021-10-09)
(2) LAN port
(6) AC OUT power
output ports
(10) DO/DI ports
(14) Spare fuse box
Specifications
● AC IN: one AC input, 90 V AC to 240 V AC
● 48 V DC input: terminal, with an input voltage of 36 V DC
to 60 V DC
● AC OUT1: two AC outputs, 90 V AC to 240 V AC. The
maximum current of two outputs is 5 A.
● AC OUT2: one AC output, 90 V AC to 240 V AC. The
maximum current is 5 A.
FE communication with a communications rate of 10/100
Mbit/s
Copyright © Huawei Technologies Co., Ltd.
(3) RS485 ports
(COM1/COM2)
(7) Terminal cover
(11) DO/12V port
(15) Indicators
3 Device Description
(4) RS485 port
(reserved)
(8) AC IN power input
port
(12) AI/DI ports
(16) BLINK button
45