ECC800 Data Center Controller
User Manual
----End
6.9 Battery Management
If iBOXs and iBATs are configured, perform the following steps to commission
them.
6.9.1 Setting iBOX and iBAT Parameters
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose Monitoring > Power Distribution > iBOX > Running Parameters.
Step 3 Click Unhide All Advanced Signals, set iBOX single battery qty., Batt.
installation time, Single battery capacity, Current source, and Battery string
No.. Retain default values for other parameters.
Table 6-52 Setting iBOX parameters
Parameter
iBOX single
battery qty.
Batt installation
time
Single battery
capacity
Issue 04 (2021-10-09)
Figure 6-91 Viewing historical PUE data
Description
Total number of batteries
monitored by the iBOX
Actual time at which batteries are
installed
Single battery capacity refers to the
capacity of a single battery in a
battery string managed by the
iBOX.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
Remarks
Set this parameter
based on the battery
parameter planned by
the customer.
-
Obtain the battery
capacity from the
battery label or
document.
240