How Can I Add An Rs485 Device Connected To The Ecc800-Pro Through A Uim20A - Huawei SmartDC V100R021C10 User Manual

Data center controller
Hide thumbs Also See for SmartDC V100R021C10:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Path
NOTE
Monitoring >
System > ECC800
> Running
Parameters, click
Unhide All
Advanced
Signals, click
Power Supply
Parameters.
Step 3 After setting all mandatory parameters, click Submit.
----End
Follow-up Procedure
Choose Home > Plan View on the ECC800-Pro WebUI, and drag the device to the
corresponding position in the Smart Module View pane based on the actual
device layout.
8.31 How Can I Add an RS485 Device Connected to the
ECC800-Pro Through a UIM20A?
Prerequisites
This section uses the device (such as a T/H sensor, rPDU, cabinet electronic lock,
and U-bit manager) connecting to the COM1 port on the UIM20A expansion
module as an example.
Procedure
Step 1 Set communications parameters on the device.
Issue 04 (2021-10-09)
Parameter
AI/DI_3
The setting
sensor type
example indicates
that the device
connects to the
AI/DI_3 port on
the ECC800-Pro. If
the device
connects to
another port,
enter the number
of the connected
port.
II power
supply
enable(AIDI_
3/COM2/
AIDI_5)
Copyright © Huawei Technologies Co., Ltd.
Setting
Select the type of the device to be accessed
from the drop-down list box.
NOTE
Devices except the normally open devices,
normally closed devices, door status switch, and
water sensor (electrode-type) can be
automatically identified after they are
connected.
The default value is Enable.
8 FAQ
375